York PS8*DH Air Conditioner User Manual


 
279744-YTG-A-0407
Unitary Products Group 5
HORIZONTAL SIDEWALL VENTING
For applications where vertical venting is not possible, the
only approved method of horizontal venting is the use of an
auxiliary power vent. Approved power venters are Fields
Controls Model SWG-4Y or the appropriate Tjernlund GPAK
model. Follow all application and installation details provided
by the manufacturer of the power vent. This unit may be hori-
zontally vented using 4” (10.2 cm) diameter pipe with a mini-
mum length of 4.5 feet (1.37 m) and a maximum length of
34.5 feet (10.82 m) with up to 4 elbows.
FILTER PERFORMANCE
The airflow capacity data published in Blower Performance
Tables above, represents blower performance WITHOUT fil-
ters. To determine the approximate blower performance of
the system, apply the filter drop value for the filter being used
or select an appropriate value from the Table below.
NOTE: The filter pressure drop values in Blower Perfor-
mance Tables are typical values for the type of filter listed and
should only be used as a guideline. Actual pressure drop rat-
ings for each filter type vary between filter manufacturer.
NOTES:
1. Air velocity through throwaway type filters may not exceed 300
feet per minute. All velocities over this require the use of high
velocity filters.
RECOMMENDED FILTER SIZES
Cabinet Size Top Return (in)
A (2) 14 x 20
B (2) 14 x 20
C (2) 14 x 20
D (2) 14 x 20
FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)
Airflow Range
Minimum
Opening Size
Filter Type
Disposable Washable Fiber Pleated
CFM
in
2
In W.C. In W.C. In W.C.
0 - 750 230 0.01 0.01 0.15
751 - 1000 330 0.05 0.05 0.20
1001 - 1250 330 0.10 0.10 0.20
1251 - 1500 330 0.10 0.10 0.25
1501 - 1750 380 0.15 0.14 0.30
1751 - 2000 380 0.19 0.18 0.30
2001 & Above 463 0.19 0.18 0.30
UNIT CLEARANCES TO COMBUSTIBLES
Application
Top Front Rear
Left
Side
Right
Side
Flue
Floor/
Bottom
Closet Alcove Attic
Line
Contact
In. In. In. In. In. In.
Downflow 160036
1
1
Yes Yes Yes No
Downflow B-Vent130001
1
1
Yes Yes Yes No
Horizontal 160036CombustibleNoYesYes
Yes
2
Horizontal B-Vent 1 3 0 0 0 1 Combustible No Yes Yes
Yes
2
1 Special floor base or air conditioning coil required for use on combustible floor.
2 Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace-
jacket and building joists, studs or framing.