COOLING CAPACITY - Coil Only
*
MODEL
RATED
CFM
ENTERING
AIR °F
(WET BULB)
MBH @ EVAPORATOR TEMPERATURE AND CORRESPONDING
PRESSURE °F / PSIG
35 / 61.5 40 / 68.5 45 / 76.0 50 / 84.0
UPFLOW "A" TYPE
G1FA024S14(T)
G1UA024S14
675
72 35.6 32.5 29.0 25.2
67 32.9 29.7 26.3 22.7
62 27.0 23.9 20.7 17.4
57 21.9 19.0 15.9 12.4
G1FA024S17(T)
G1UA024S17
850
72 35.6 32.5 29.0 25.2
67 32.9 29.7 26.3 22.7
62 27.0 23.9 20.7 17.4
57 21.9 19.0 15.9 12.4
G1FA030S14(T)
G1UA030S14
1025
72 38.9 35.4 31.6 27.6
67 33.9 30.3 26.8 23.0
62 27.3 23.7 22.5 18.0
57 22.6 20.1 17.5 14.8
G1FA036S14(T)
G1FA036S17(T)
G1UA036S14
G1UA036S17
1250
72 51.1 46.5 41.5 36.6
67 40.9 36.1 31.7 26.9
62 32.0 26.8 29.3 21.8
57 27.4 25.4 23.4 21.8
G1FA036S21(T)
G1UA036S21
1250
72 51.1 46.5 41.5 36.6
67 40.9 36.1 31.7 26.9
62 32.0 26.8 29.3 21.8
57 27.4 25.4 23.4 21.8
G1FA048S17(T)
G1FA048S21(T)
G1UA048S17
G1FUA048S21
1620
72 99.4 85.5 71.2 56.2
67 79.6 66.8 54.4 41.6
62 62.1 49.4 40.2 33.7
57 53.3 46.7 40.2 33.7
G1FA060S21(T)
G1FA060S24(T)
G1UA060S21
G1UA060S24
1850
72 118.7 100.0 81.1 61.5
67 95.0 78.4 61.9 45.4
62 74.0 58.0 45.7 36.7
57 63.6 54.8 45.7 36.7
* - See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.
(T) indicates models with factory installed thermal expansion valve.
Coil Only
*
MODEL
RATED
CFM
ENTERING
AIR °F
(WET BULB)
MBH @ EVAPORATOR TEMPERATURE AND CORRESPONDING PRESSURE
°F/ PSIG
35 / 61.5 40 / 68.5 45 / 76.0 50 / 84.0
HORIZONTAL DUCT TYPE
G1HD024 815
72 35.3 32.4 28.7 24.9
67 32.6 29.4 26.0 22.5
62 26.7 23.7 20.5 17.2
57 21.7 18.8 15.7 12.3
G1HD036 1192
72 57.9 52.7 47.1 41.5
67 46.4 41.1 35.9 30.4
62 36.2 30.4 26.5 24.7
57 31.1 28.7 26.5 24.7
G1HD048 1610
72 83.4 71.7 59.7 47.1
67 66.8 56.1 45.6 34.9
62 52.1 41.5 33.7 28.3
57 44.7 39.2 33.7 28.3
G1HD060 2100
72 133.0 112.4 90.9 69.2
67 106.5 87.9 69.4 50.0
62 83.0 65.0 51.3 41.1
57 71.2 61.4 51.3 41.1
* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.