York E*FH060 Air Conditioner User Manual


 
036-21031-004 Rev. A (0603)
Unitary Products Group 23
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO E4FH060S06
EVAPORATOR COIL MODEL NO G2FD060(S,H)24
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1700 1850 2000
MBTUH K.W. C.O.P. MBTUH K.W. C.O.P. MBTUH K.W. C.O.P.
60
60 69.24.904.1969.84.814.3170.54.724.43
70 67.45.273.8068.75.183.9369.95.104.07
80 65.75.733.4067.55.643.5569.25.553.70
47
60 61.44.723.8262.84.703.9264.24.684.02
70 58.85.063.4160.05.033.5061.25.003.59
80 56.15.493.0057.15.453.0758.15.413.15
40
60 58.84.693.6659.44.683.7160.14.673.76
70 55.14.993.2355.34.953.2755.44.913.30
80 51.55.372.8051.15.302.8250.75.242.84
30
60 50.04.513.2351.04.503.3152.04.483.39
70 48.64.882.9048.74.842.9348.74.802.96
80 47.15.342.5846.35.282.5645.45.222.54
17
60 40.14.322.7240.94.332.7741.74.332.82
70 39.44.702.4640.04.692.5040.64.682.54
80 38.75.162.2039.15.152.2339.65.132.26
10
60 36.84.242.5737.44.262.6038.14.282.63
70 34.94.602.2435.34.612.2735.84.632.29
80 33.05.071.9233.25.081.9333.55.091.95
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
F2FP060 1.00 1.03 0.97
F2FV060 1.00 1.17 0.86
G2FD061H24 1.03 1.00 1.03