York DR120 Air Conditioner User Manual


 
246721-YTG-C-0606
26 Unitary Products Group
TABLE 11: ELECTRICAL DATA DR090 W/O PWRD CONVENIENCE OUTLET
RLA LRA FLA 1.5 2 1.5 2 1.5 2 1.5 2 1.5 2
ea. ea. ea. HP HP HP HP HP HP HP HP HP HP
None -- -- 38.7 40.7 44.2 46.2 50 50 50 50
2TP04520925 6.8 18.9 38.7 40.7 44.2 46.2 50 50 50 50
2TP04521825 13.5 37.5 54.6 57.1 61.5 64.0 60 60 70 70
2TP04522425 18.0 50.0 70.2 72.7 77.1 79.6 80 80 80 80
2TP04523625 25.5 70.8 96.2 98.7 103.1 105.6 100 100 110 110
None -- -- 38.7 40.7 44.2 46.2 50 50 50 50
2TP04520925 9.0 21.7 38.7 40.7 44.2 46.2 50 50 50 50
2TP04521825 18.0 43.3 61.9 64.4 68.8 71.3 70 70 70 80
2TP04522425 24.0 57.7 79.9 82.4 86.8 89.3 80 90 90 90
2TP04523625 34.0 81.8 110.0 112.5 116.9 119.4 110 125 125 125
None -- -- 19.8 20.8 22 23 25 25 25 25
2TP04520946 9 11.3 19.8 20.8 22 23 25 25 25 25
2TP04521846 18 22.6 30.9 32.2 33.7 34.9 35 35 35 35
2TP04522446 24 30.1 40 41.2 42.7 44 40 45 45 45
2TP04523646 34 42.7 55 56.2 57.7 59 60 60 60 60
None -- -- 15.1 16.3 16.9 18.1 20 20 20 20
2TP04520958 9 9.0 15.1 16.3 16.9 18.1 20 20 20 20
2TP04521858 18 18.1 24.7 26.2 26.9 28.4 25 30 30 30
2TP04522458 24 24.1 31.9 33.4 34.1 35.6 35 35 35 40
2TP04523658 34 34.1 43.9 45.4 46.1 47.6 45 50 50 50
* Maximum HACR breaker of the same AMP size is applicable.
2.4 3.6 1.8 0.0
575
5.1 44.0 0.6
3.1 4.1 2.2 0.0
460
6.7 54.0 0.8
0.0
230
13.1 110.0 1.5 6.2 8.2 5.5 0.0
Max Fuse* Size
w/Power
Exhaust (Amps)
FLA FLA
208
13.1 110.0 1.5 6.2 8.2 5.5
Heater
Amps
Min. Circuit
Ampacity
(Amps)
MCA w/Power
Exhaust (Amps)
Max Fuse* Size
(Amps)
Pwr Exh
Motor
Pwr
Conv
Outlet
Electric Heater
Model No.
Actual
KW
Voltage
Compressors
OD Fan
Motors
Supply Blower
Motor FLA
TABLE 12: ELECTRICAL DATA DR090 WITH PWRD CONVENIENCE OUTLET
RLA LRA FLA 1.5 2 1.5 2 1.5 2 1.5 2 1.5 2
ea. ea. ea. HP HP HP HP HP HP HP HP HP HP
None -- -- 48.7 50.7 54.2 56.2 60 60 60 60
2TP04520925 6.8 18.9 48.7 50.7 54.2 56.2 60 60 60 60
2TP04521825 13.5 37.5 67.1 69.6 74.0 76.5 70 70 80 80
2TP04522425 18.0 50.0 82.7 85.2 89.6 92.1 90 90 90 100
2TP04523625 25.5 70.8 108.7 111.2 115.6 118.1 110 125 125 125
None -- -- 48.7 50.7 54.2 56.2 60 60 60 60
2TP04520925 9.0 21.7 48.7 50.7 54.2 56.7 60 60 60 60
2TP04521825 18.0 43.3 74.4 76.9 81.3 83.8 80 80 90 90
2TP04522425 24.0 57.7 92.4 94.9 99.3 101.8 100 100 100 110
2TP04523625 34.0 81.8 122.5 125.0 129.4 131.9 125 125 150 150
None -- -- 24.8 25.8 27 28 30 30 30 30
2TP04520946 9 11.3 24.8 25.8 27 28 30 30 30 30
2TP04521846 18 22.6 37.2 38.4 39.9 41.2 40 40 40 45
2TP04522446 24 30.1 46.2 47.5 49 50.2 50 50 50 60
2TP04523646 34 42.7 61.2 62.5 64 65.2 70 70 70 70
None -- -- 19.1 20.3 20.9 22.1 20 25 25 25
2TP04520958 9 9.0 19.1 20.3 21.1 22.6 20 25 25 25
2TP04521858 18 18.1 29.7 31.2 31.9 33.4 30 35 35 35
2TP04522458 24 24.1 36.9 38.4 39.1 40.6 40 40 40 45
2TP04523658 34 34.1 48.9 50.4 51.1 52.6 50 60 60 60
* Maximum HACR breaker of the same AMP size is applicable.
2.4 3.6 1.8 4.0
575
5.1 44.0 0.6
3.1 4.1 2.2 5.0
460
6.7 54.0 0.8
6.2 8.2 5.5 10.0
230
13.1 110.0 1.5
FLA FLA
208
13.1 110.0 1.5 6.2 8.2 5.5 10.0
Min. Circuit
Ampacity
(Amps)
MCA w/Power
Exhaust (Amps)
Max Fuse* Size
(Amps)
Max Fuse Size
w/Power
Exhaust (Amps)
Voltage
Compressors
OD Fan
Motors
Supply Blower
Motor FLA
Pwr Exh
Motor
Pwr
Conv
Outlet
Electric Heater
Model No.
Actual
KW
Heater
Amps