Physical and Electrical Data
MODEL
CZH02411 CZH03611 CZH04811 CZH06011
Unit Supply Voltage 208-230V, 1φ, 60Hz
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 15.6 23.6 29.2 34.8
Max. Overcurrent Device Amps
2
25 40 50 60
Min. Overcurrent Device Amps
3
20 25 30 35
Multi-stage Compressor Yes Yes Yes Yes
Compressor Type Scroll Scroll Scroll Scroll
Compressor Amps
Rated Load 10.3 16.7 21.2 25.6
Locked Rotor 52 82 96 118
Crankcase Heater No No No No
Fan Motor Amps Rated Load 2.8 2.8 2.8 2.8
Fan Diameter Inches 24 24 24 24
Fan Motor
Rated HP 1/3 1/3 1/3 1/3
Nominal RPM 685 685 685 685
Nominal CFM 2900 3200 3100 3150
Coil
Face Area Sq. Ft. 23.58 23.58 23.58 23.58
Rows Deep 2 2 2 2
Fins / Inch 16 16 14 14
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed) 3/4 3/4 7/8 7/8
Unit Charge (Lbs. - Oz.)
4
15 - 1 13 - 7 12 - 9 13 - 5
Charge Per Foot, Oz. 0.62 0.62 0.67 0.67
Operating Weight Lbs. 305 305 310 330
1 Rated in accordance with ARI Standard 110, utilization range “A”.
2 Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3 Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4 The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
VAPOR
LIQUID
2-3/8
3-1/8
6-1/2
C
A
B
Unit
Model
Dimensions
(Inches)
Refrigerant
Connection
Service Valve Size
A B C Liquid Vapor
24 39-1/2 42 34
3/8”
3/4”
36 39-1/2 42 34
48 39-1/2 42 34
7/8”
60 39-1/2 42 34