York BQ 036 Heat Pump User Manual


 
036-21508-005-A-0305
26 Unitary Products Group
TABLE 15: ELECTRICAL DATA - BQ060 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 49.0 80
2CE04510506 4.0 19.2 73.1 100
2CE04510706 5.6 26.9 82.7 100
2CE04511006 8.0 38.5 97.1 110
2CE04511506 11.9 57.2 120.5 125
2CE04512006 15.9 76.4 144.6 150
2CE04513006 22.2 106.7 182.4 200
NONE 0.0 0.0 49.0 80
2CE04510506 5.3 22.1 76.6 100
2CE04510706 7.5 31.3 88.1 110
2CE04511006 10.6 44.2 104.2 125
2CE04511506 15.9 66.3 131.8 150
2CE04512006 21.2 88.3 159.4 175
2CE04513006 29.6 123.3 203.2 225
NONE 0.0 0.0 33.0 50
2CE04510525
2
4.0 11.1 46.9 60
2CE04510725
2
5.6 15.5 52.5 60
2CE04511025 8.0 22.2 60.8 70
2CE04511525 11.9 33.0 74.3 80
2CE04512025 15.9 44.1 88.2 90
2CE04513025 22.2 61.6 110.1 125
NONE 0.0 0.0 33.0 50
2CE04510525
2
5.3 12.7 49.0 60
2CE04510725
2
7.5 18.0 55.6 70
2CE04511025 10.6 25.5 64.9 70
2CE04511525 15.9 38.2 80.8 90
2CE04512025 21.2 51.0 96.8 100
2CE04513025 29.6 71.2 122.0 125
NONE 0.0 0.0 17.1 25
2CE04510746
2
6.8 8.2 27.3 35
2CE04511046
2
10.1 12.1 32.3 35
2CE04511546
2
13.6 16.4 37.5 40
2CE04512046
2
19.5 23.5 46.4 50
2CE04513046
2
28.8 34.6 60.4 70
NONE 0.0 0.0 13.6 20
2CE04511058 10.6 10.2 26.3 30
2CE04511558 15.9 15.3 32.7 35
2CE04512058 21.2 20.4 39.1 40
2CE04513058 30.4 29.3 50.1 60
ID Blower
Motor
FLA
Conv
Outlet
Amps
Max Fuse /
BRKR
1
Size
Amps
RLA
Each
LRA
Each
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Model
Tonnage
Voltage
Compressors
OD Fan
Motor
FLA
1.3 3.3 0.0
575-3-60 7.9 50 1.3 3.3 0.0
2.3 6.6 0.0
230-3-60 19.3 137 2.3 6.6 0.0
208-3-60
2.3 6.6 0.0
230-1-60 32.1 148 2.3 6.6 0.0
5
208-1-60 32.1 148
19.3 137
460-3-60 10.0 62
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.