York 36 Air Conditioner User Manual


 
255040-YTG-A-0506
Unitary Products Group 7
TABLE 1: SOUND POWER RATING
1
UNIT
SIZE
CFM
ESP BLOWER
SOUND POWER (db 10
-12
Watts)
Octave Band Centerline Frequency (Hz)
SWL
dB(A)
dB(A)
@
10Ft.
2
IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000
036 1,200 0.6 LOW 0.60 84 84 74 67 69 62 57 52 74 41
048 1,600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42
060 2,000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43
072 2,2000.3HIGH1.3587877770726560557744
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-
tee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS - (ARI 210/240)
1
1. 80/67°F Indoor and 95°F outdoor.
MODEL MBH
EER
2
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
SEER
3
3. SEER = Seasonal Energy Efficiency Ratio.
D(CE, CG)036
36.0 9.1 10.0
D(CE, CG)048
47.4 9.0 10.0
D(CE, CG)060
59.0 9.1 10.0
D(CE, CG)072
72.0 9.0 -
TABLE 3: GAS HEAT RATINGS
1
1. All units are single-stage heating.
MODEL
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
DCG036N040
DCG036N079
50
100
40
80
80.9
80.5
15 - 45
40 - 70
DCG048N060
DCG048N099
75
125
60
100
80.9
80.3
25 - 55
45 - 75
DCG060N079
DCG060N099
100
125
80
100
80.5
80.3
25 - 55
35 - 65
DCG072N079
DCG072N099
100
125
80
100
80.5
80.3
25 - 55
35 - 65