York 36 Air Conditioner User Manual


 
255040-YTG-A-0506
12 Unitary Products Group
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1700 835 705 880 745 923 795 969 860 1013 970 ----
1600 811 655 854 695 898 740 942 790 986 840 1029 900 - -
1500 782 610 827 650 871 685 917 730 960 775 1003 825 1046 905
1400 - - 798 595 844 640 889 680 932 720 975 765 1018 790
1300 ----816590862635907675951715995750
1200 ------834585881630927665970705
1100 ------809550855590900625942665
1000 ------782510829545872858919625
900--------797500843540890580
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1700 --------------
1600 --------------
1500 --------------
1400 1055 875 ------------
1300 1036 780 1066 850 ----------
1200 1011 735 1047 765 1075 800 --------
1100 987 690 1028 720 1060 750 1084 775 ------
1000 963 655 1005 680 1040 695 1068 715 1089 735 ----
900 936 615 980 645 1020 660 1050 670 1053 680 1090 690 - -
0.60 0.70 0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20 0.30 0.40 0.50
UNIT
TONNAGE
AIR
FLOW
CFM
3
1,2
UNIT
TONNAGE
AIR
FLOW
CFM
3
1, 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90 1.00 1.10 1.20 1.30 1.40 1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on a
pp
lications other than
g
as / electric units with side duct airflows.