White Rodgers 37-6186B Heat Pump User Manual


 
5
* NOTE: COMP LOCK OFF permanently
defeats compressor lockout. You must turn
this selection ON if you do not have a
system that already provides compressor
short-cycle protection. Please see “Lockout
Bypass Option” to temporarily override
compressor lockout.
INSTALLER TABLE
1
2
HEAT PUMP
(1)
2 OR 3
3
ELECT HEAT FAN
(ON)
OFF
Fan cycles with call for Emergency heat if ON.
Fan always cycles with pump stages.
4
SET CYCLE HEAT
(13)
9 to 40
5
SET CYCLE COOL
(13)
9 to 40
12
ECON
(OFF)
ON
15
REMT SEN b
(OFF)
ON
16
REMT SEN C
(OFF)
ON
Returns to normal operation
STAT SEN L
(ON)
OFF
13
HEAT-EMER-OFF-COOL-
AUTO
HEAT-EMER-OFF-COOL
14
REMT SEN A
(OFF)
ON
Selects Remote Sensor A (connected to SA) if ON.
Selects:
1. one compressor on Y1.
2. two compressors on Y1, Y2.
3. one compressor on W1.
Selects HEAT anticipation adjustment.
Selects COOL anticipation adjustment.
Allows selection of HEAT, EMER and COOL or
HEAT, EMER, COOL and AUTO with SYSTEM
button.
Economizer option. Long Y1 cycles for cooling
with outdoor air
Selects Remote Sensor B (connected to SB) if ON.
Selects Remote Sensor C (connected to SC) if ON.
When OFF, disables local sensor if a remote sensor
is enabled.
PROGRAM
RUN
SET
and SET
(hold for approx.
3 seconds)
TIME
DAY
FWD
FWD
FWD
FWD
FWD
FWD
FWD
FWD
FWD
6
SET CYCLE AUX
(06)
1 to 40
9
HEAT FAN DELAY OFF
(00)
0 to 127 seconds
10
PUMP
(ON)
OFF
11
COMP LOCK
(OFF)
ON
7
COOL FAN DELAY OFF
(00)
0 to 127 seconds
8
4
4
4
4
4
6
6
6
7
6
6
4
6
6
6
6
6
FAN DELAY ON
(01)
1 to 30 seconds
Selects time delay for fan ON for compressor stages.
Selects time delay for COOL fan OFF.
Selects AUXILIARY stage anticipation adjustment.
Selects time delay for HEAT fan OFF in Emergency
mode only when ELECT HEAT FAN (Step 2) is ON.
Fossil Fuel Kit Alternative option. Turns compressor
OFF if Auxiliary is ON for longer than one minute.
(Heat Pump 1 & 2)
Selects compressor short-cycle protection enabled
or OFF.*
TIME
TIME
TIME
TIME
TIME
TIME
TIME
TIME
TIME
TIME
TIME
TIME
TIME
TIME
TIME
FWD
FWD
FWD
FWD
FWD
FWD
Step Press Button(s) Displayed (Factory Default) Press or to select: COMMENTS
See
Page
NOTE: You must be in the User
Configuration Menu to enter the
Installer Menu. Press TIME
FWD
and TIME
BACK