White Rodgers 1F85ST-0422 Thermostat User Manual


 
4
INSTALLER/CONFIGURATION MENU
With thermostat in Heat, Cool or Auto, in normal operation, press the Menu button for at least 5 seconds. The display will
show item #1 in the table below. Press Menu to advance to the next menu item. Press or to change an item option.
Shaded items are not available to 1F86.
INSTALLER/CONFIGURATION MENU
MENU
REF.
HP SS
PRESS
BUTTON
DISPLAYED
(FACTORY DEFAULT)
Press
or to
select from listed options
COMMENTS
1 1 1 MENU (EM2) bC1, ES1 Selects Multi-Stage (EM2 No Heat Pump),
Heat Pump 1 (bC 1, 1 compressor),
or Single Stage (ES1)
2 2 2 MENU (GAS) for ES1 or EM2
(ELE) for bC
ELE GAS setting: furnace controls the blower
ELE setting: thermostat controls the blower
3 3 3 MENU CE (0)
(Disabled)
1, 2, 3, 4, 5, 6 Selects Cool Savings
Value 1 (low) to 6 (high), Value 0 Disables Feature
4 4 4 MENU E (On) OFF
Selects Energy Management Recovery (EMR)
On or OFF.
5
5 MENU CR Calor (ME) AL, bA Adjustable Anticipation:
Selects heating cycle rate for MS or SS
6 5
MENU CR Bomba de Calor
(ME)
AL, bA Adjustable Anticipation (Heat Pump) (only
when heat pump selected in #1)
7 6 6 MENU CR Frio (ME)
or
CR Aux (FA)
AL, bA
AL
Adjustable Anticipation:
Selects the cycle rate for cooling
(only when Em 2 or ES 1 is selected in item 1.)
or Selects the cycle rate for Emergency
mode and Auxiliary stage if Heat Pump
is selected in item 1.
8 7 7 MENU Cd (OFF) Cd On Compressor Lockout Time
9 8 8 MENU Frio Off
Calor Auto
Calor Frio Off,
Calor Off with Vent icon,
Calor Off without Vent
icon Frio Off, Auto Off
System Mode Confi guration
with Automatic Changeover capability
10 9 9 MENU L (On) L OFF Selects Display Light On or OFF
11 10 10 MENU 0
(current temperature)
1 AL, 2 AL, 3 AL, 4 AL,
1 bC, 2 bC, 3 bC, 4 bC
Adjustable Ambient Temperature Display
12 11 11 MENU
°F °C
Selects Fahrenheit/Celsius Temperature Display
13 12 12 MENU L Calor
(90)
L 62 to L 89 Selects Limited Calor (HEAT) Range
14 13 13 MENU L Frio
(45)
L 46 to L 82 Selects Limited Frio (COOL) Range
15 14 14 MENU P3 P0, P2
Defaults for 5-1-1 programming (P3) but non-
programmable (PO) or 5-2 programming (P2)
is available on most models.
16 15 15 MENU Calor AP (On)
OFF Automatic Schedule for heat mode.
NA to Cool only system.
17 16 16 MENU Frio AP (On) OFF
Automatic Schedule for cool mode.
NA to Heat only system.
18 17
MENU Calor AL (On) OFF Fast Heat option may be disabled by
selecting OFF. NA to ES confi g.
NA to Cool only system.
19 18
MENU Frio AL (On) OFF Fast Cool option may be disabled by ES or bC
selecting OFF. NA to ES confi g.
NA to Heat only system.
20 19 17 MENU Hv (On) OFF
Selects Automatic daylight Savings Time
option On or OFF.
21 20 18 MENU Cambiar Filtro (OFF) On Selects Filter Change-out Indicator On or OFF.
MENU Cambiar Filtro (200 h) 25-1975 h Change Filter time in 25 hour increments. This
menu only appears if On is selected in above.
22 21 19 MENU Frio On (o) Calor On (b)
Selects operation of the reversing valve terminal
(O/B) output as an O or B terminal.
22 20
Arrancar
Returns to Normal Operation