Whirlpool ACE082XH0 Air Conditioner User Manual


 
4
Recommended grounding method
For your personal safety, this air conditioner must be grounded.
This air conditioner is equipped with a power supply cord with a
3-prong grounding plug. To minimize possible electrical shock
hazard, the cord must be plugged into a mating 3-prong
grounding-type outlet, grounded in accordance with all local
codes and ordinances. If a mating 3-prong grounding-type outlet
is not available, it is the consumer’s responsibility to have a
properly grounded, 3-prong outlet installed by a licensed
installer.
It is the customer’s responsibility:
• To contact a qualified electrical installer.
• To assure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70 —
latest edition,* and all local codes and ordinances.
Copies of the standards listed may be obtained from:
* National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts 02269
Specific electrical requirements are listed in the chart. Follow the
requirements for the type of plug on the power supply cord.
Método recomendado para la puesta
a tierra
Para su seguridad personal, este aparato debe ser puesto a tierra. Este
acondicionador de aire está equipado con un cordón eléctrico provisto
de un enchufe con clavija tripolar de conexión a tierra. Para reducir a
un mínimo el riesgo posible de un choque eléctrico, el cordón debe
enchufarse en un tomacorriente mural para clavija con 3 terminales
puesto a tierra de acuerdo con todos los códigos y reglamentos locales.
Si no se dispone de un tomacorriente para clavija tripolar, es
responsabilidad y obligación personal del cliente hacer instalar un
tomacorriente para clavija con tres terminales debidamente puesto a
tierra por un electricista calificado.
Es responsabilidad del cliente:
• Llamar a un instalador eléctrico calificado.
• Asegurarse de que la instalación eléctrica es adecuada y de acuerdo
con el Código Nacional de Energía, ANSI/NFPA 70, última edición*, y
todos los códigos y reglamentos locales.
Pueden obtenerse copias de las normas señaladas del:
* National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts 02269
Los requerimientos eléctricos específicos se indican en la tabla. Siga los
requerimientos para el tipo de enchufe en el cordón de alimentación
eléctrica.
Wiring requirements Requerimientos de cableado
• 115 volt (103.5 min. - 126.5 max.)
• 0-12 amperes
• 15-amp time-delay fuse or circuit breaker
• 14 gauge copper wiring
• 230 volt (207 min. - 253 max.) or
• 230/208 volt (197.6 min. - 253 max.)
• 0-12 amperes
• 15-amp time-delay fuse or circuit breaker
• 14 gauge copper wiring
• 230 volt (207 min. - 253 max.) or
• 230/208 volt (197.6 min. - 253 max.)
• 0-16 amperes
• 20-amp time-delay fuse or double-pole circuit breaker
• 12 gauge copper wiring
• 230 volt (207 min. - 253 max.) or
• 230/208 volt (197.6 min. - 253 max.)
• 0-24 amperes
• 30-amp time-delay fuse or circuit breaker
• 10 gauge copper wiring
Power supply cord plug receptacle
Receptáculo para la clavija del cordón eléctrico
1/4"
(0.6 cm)
1/2"
(1.3 cm)
• 115 voltios (103.5 mín. - 126.5 máx,)
• 0-12 amperes
• fusible de retardo o disyuntor de 15 amperes
• cables de cobre calibre 14
• 230 voltios (207 mín. - 253 máx.) o
• 230/208 voltios (197.6 mín. - 253 máx.)
• 0-12 amperes
• fusible de retardo o disyuntor de 15 amperes
• cables de cobre calibre 14
• 230 voltios (207 mín. - 253 máx.) o
• 230/208 voltios (197.6 mín. - 253 máx.)
• 0-16 amperes
• fusible de retardo o disyuntor bipolar de 20 amperes
• cables de cobre calibre 12
• 230 voltios (207 mín. - 253 máx.) o
• 230/208 voltios (197.6 mín. - 253 máx.)
• 0-24 amperes
• fusible de retardo o disyuntor de 30 amperes
• cables de cobre calibre 10
continued from page 3 viene de la página 3