Weil-McLain STAR-34 Boiler User Manual


 
Part Number 550-110-268/0699
5
StaR-34 Venting Supplement
26801
Air pipe
Vent pipe
StaR-34
vent starter tee
Slope
Slope vent pipe downward, toward
boiler, minimum ¼” per foot.
Figure 3 GV direct vent through sidewall
(using Weil-McLain Vent/Air Intake
Termination Kit)
Figure 5 GV direct vent (using Weil-McLain
Through-Roof or Through-Unused-
Chimney Termination Kit)
26803
Slope vent pipe
downward, toward
boiler, minimum
¼” per foot.
StaR-34
vent starter tee
Select
vent
method
Figure 7 GV non-direct vent through roof
26805
Slope vent pipe
downward,
toward boiler,
minimum ¼”
per foot.
StaR-34
vent starter tee
26804
Slope vent pipe
downward, toward
boiler, minimum
¼” per foot.
StaR-34
vent starter tee
Figure 6 GV non-direct vent through sidewall
(using termination coupling)
(See WARNING above.)
26802
Vent pipe
StaR-34
vent starter tee
Slope
Slope vent
pipe
downward,
toward boiler,
minimum ¼”
per foot.
Figure 4 GV non-direct vent through sidewall
(using Weil-McLain Vent/Air Intake
Termination Kit)
(See WARNING above.)
For altitudes more than 5,500 feet above sea level — Do not use non-direct vent through
sidewall methods as shown in
Figures 4 and 6 below. Can cause severe personal injury, death
or substantial property damage if ignored.