MAINTENANCE
Button: MENU/<Maintenance>
The Maintenance menu gives access to sensor and outputs trimming and Soft-Off. In
addition, you'll have access to view the Startup configuration settings.
ALERT
To be able to change the BMC settings the Program/Run Switch must be set to
Program. The switch is located under the Enclosure Wiring Cover for security.
The Enclosure Wiring Cover can be securely closed using a lock.
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 45sec
<Output Trim>
<Configuration>
RUNPROGRAM
SYSTEM & OUTDOOR SENSOR TRIM
Adjustable from -5F°/-3C° to +5F°/+3C° Default: 0°F
Button: MENU/<Maintenance>/System Trim
Button: MENU/<Maintenance>/Outdoor Trim
The Weil McLain thermistor type sensors are very accurate, and normally require no
calibration. Sometimes it may be desirable to make small adjustments to the displayed
value for either the Outdoor temperature (OD) or the System temperature (SYS). The
Trim setting can adjust the displayed value by ± 5°F.
Do not use the Trim setting to make the Outdoor temperature sensor match that reported
on the radio or TV. Outdoor temperature can vary widely over a broadcast range. Only
trim the outdoor sensor based on an accurate thermometer reading taken where the
sensor is located.
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[]
SOFT-OFF DELAY
Adjustable from 0sec to 60sec Default: 45sec
Button: MENU/<Maintenance>/Soft-Off Delay
When a stage is no longer needed, the Soft-Off keeps that stage burner in Low Fire prior
to turning it off.
The display will show a percent that is equal to the Ignition % for the stage in Soft-Off
delay. That number will blink for the Soft-Off delay period.
If during the Soft-Off delay period the BMC needed that stage to turn back on, the stage
will be released from the Soft-Off delay and resume normal operation.
On a Shutdown initiation or Tstat termination any stage that was on will go into Soft-Off
delay before fully turning off.
BACK SAVE
------- SOFT-OFF DELAY --------
45
sec
[]
ALERT
When using Soft-Off and Last Stage Hold, the last boiler stage will not turn off until both parameters have
elapsed. In this case, Soft-Off will start after the Last Stage Hold has been reached or exceeded.
OUTPUT TRIM
Adjustable from -5 to +5 Default: 0
Button: MENU/<Maintenance>/Output Trim
Each of the stages controlled by the BMC has a separate Output Trim setting.
Output Trim acts as an adjustment to a stage output percent to match the burner motor.
After adjusting the Output Trim, test the operation to make sure the results match your
expectation.
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
ALERT
DO NOT use the Output Trim for a Stage unless it is absolutely necessary. Test
burner operation and modulation output matching after adjusting the Output Trim.