Weil-McLain 550-100-067/0608 Boiler User Manual


 
Part number 550-100-067/0608
7
g a s -f i r e d w a t e r b o i l e r User’s Information Manual
Maintenance procedures — MONTHLY
Maintenance procedures — PERIODICALLY
Test the low water cutoff (if installed)
If the system is equipped with a low water cutoff, test the low 1.
water cutoff periodically during the heating season. Follow
the low water cutoff manufacturer’s instructions.
Reset the boiler control after testing.2.
Check U-Control date and time
Check the time shown on the U-Control display.1.
If time is incorrect, set the correct date and time as shown 2.
on pages 10 and 11.
Check vent piping
Visually inspect the flue gas vent piping for any signs of block-1.
age, leakage or deterioration of the piping. Notify your quali-
fied service technician at once if you find any problem.
Failure to inspect the vent system as noted above
and have it repaired by a qualifed service technician
can result in vent system failure, causing severe
personal injury or death.
Check air piping
Visually inspect the air inlet to be sure it is unobstructed. 1.
Inspect entire length of air piping to ensure piping is intact
and all joints are properly sealed.
Call your qualified service technician if you notice any 2.
problems.
Check the relief valve
Inspect the boiler relief valve and the relief valve discharge 1.
pipe for signs of weeping or leakage.
If the relief valve often weeps, the expansion tank may not be 2.
working properly. Immediately contact your qualified service
technician to inspect the boiler and system.
Check the condensate drain system
While the boiler is running, check the discharge end of the 1.
condensate drain tubing and the open top of the condensate
tee at the boiler (see Figure 3, page 10 for locations). Make
sure no flue gas is escaping from the condensate drain tubing
or tee by holding your fingers in front of the opening.
If you notice flue gas escaping, this indicates a dry conden-2.
sate drain trap. See step 4 for procedure to fill trap. Call
your qualified service technician to inspect the boiler and
condensate line and refill the condensate trap if problem
persists regularly.
Under some circumstances an Ultra vent system
may not produce enough condensate to keep the
condensate trap full of liquid. If the trap is not full,
small amounts of flue products can be emitted into
the boiler room through the condensate drain line
or tee. Follow procedure below to fill trap.
Verify that the condensate drain line is unobstructed by 3.
slowly pouring water into the top of the PVC tee on the side
of the boiler. The water should run out the end of the con-
densate drain line. If the water does not run out, call your
qualified service technician to inspect the boiler and clean
or replace the condensate drain line.
To fill the condensate trap, if necessary, temporarily plug the 4.
end of the condensate drain line. Then slowly pour water into
the ½ inch plastic tee on boiler right side. Pour until water
fills drain line, then overflows into the boiler trap tubing.
When water fills up to top of ½ inch tee, stop filling. Remove
temporary plug from end of condensate drain line.
Check automatic air vents (if used)
See illustration at right. 1.
Remove the cap from any automatic 2.
air vent in the system and check oper-
ation by depressing valve “B” slightly
with the tip of a screwdriver.
If the air vent valve appears to be 3.
working freely and not leaking,
replace cap “A”, twisting all the way
on.
Loosen cap “A” one turn to allow vent 4.
to operate.
Have vent replaced if it does not 5.
operate correctly.