Limit Control Mode
High limit control
Latched manual reset with ±1.7°C (3°F) hysteresis
Can only be reset when process temperature drops below limit
set point. Terminals are provided for remote reset in the event of
an overtemperature condition. (Reset switch supplied by user.)
On-off Temperature Control Mode
Off when process temperature exceeds factory-fixed or remote
adjustable set point
On when process temperature is less than factory-fixed or
remote adjustable set point
Hysteresis (switching differential) ±1.7°C (3°F) nominal
Agency Approvals
and , File #E43684
197 Commercial Cooking Appliances
873 Temperature Indicating and Regulating Equipment
991 Test for Safety Related Controls Employing Solid State
Devices
#C3236001 approved, Gas Appliance Thermostat, ANSI
Z21.23
CE 89/336/EEC Electromagnetic Compatibility Directive
EN61326, Immunity, Class B Emissions
CE 73/23/EEC Low Voltage Directive
EN60730-1, EN60730-2-9, Safety
Operator Interface
Non-adjustable, factory-fixed or remote adjustable set point
Remote Set Point
Dial scale calibrated to compensate for sensor non-linearity
Dual °F/°C scales
Accuracy
Adjustable Set Point
Calibration accuracy: ±1% of span, at 25°C ±3°C (77°F ±5°F)
ambient and rated line voltage ±1%
Set point accuracy: ±3% of dial scale
Accuracy span: 540°C (1000°F) minimum
Fixed Set Point
Calibration accuracy: ±6°C±/10°F of setting, at 25°C ±3°C (77°F
±5°F) ambient and rated line voltage ±1%
Thermocouple Stability
Thermocouple: Typically 9µV/°C ambient (±5µV/°F ambient) input
referenced
RTD: Typically 0.2°C/°C ambient (0.2°F/°F ambient)
Voltage Stability
±0.01% of span (min span of 540°C or 1000°F) per % of rated
line voltage
Thermocouple Input
Grounded or ungrounded Type E, J, K or T. Sensor break
protection de-energizes output.
Factory-set, thermocouple ranges
Output
Electromechanical relay
1
, SPDT, 3A @ 120/240V~ or 3A @
30VÎ (dc), Form C, with RC suppression on on-off temperature
controller version. Off-state output impedance is 20kwith RC
suppression.
Output Relay Status Upon Power Restoration
(Assuming process temperature is not above set point.)
Auto reset: Output relay automatically re-energizes
Manual reset: Manual reset is required to re-energize output relay
Line Voltage/Power
120V~, ±10%; (108-132V~), 50/60Hz, ±5%
208/240V~, ±10%; (187-264V~), 50/60Hz, ±5%
Power consumption 4VA maximum
Operating Environment
0 to 65°C (32 to 149°F)
0 to 90% RH, non-condensing
Storage Temperature
-40 to 85°C (-40 to 185°F)
Terminals
14 inch quick connect lugs (spade/ appliance)
Dimensions
Controller
Length 102mm (4 in.)
Width 70mm (2.8 in.)
Height 103mm (4.05 in.)
Controller Weight 0.36kg (0.79 lb.)
Shipping Weight 0.57kg (1.25 lbs.)
Set Point Assembly
Dial Scale 76mm (3 in. sq.)
Pot Depth Behind 25mm (1.0 in.)
Knob Depth in Front 31mm (1.2 in.)
Lead Length 610mm (24 in.)
Weight 0.09kg (0.2 lb.)
1
Electromechanical relays are warranted for 100,000 closures
only.
UL® is a registered trademark of Underwriter’s Laboratories, Inc.
Note: Specifications subject to change without notice.
US
®
Specifications