Vanguard Heating VP2000BTC Gas Heater User Manual


 
14
103876
CONNECTING
TO GAS
SUPPLY
The installer must supply an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce incoming gas pressure to between 11 and
14 inches of water. If you do not reduce incoming gas pressure, heater regulator
damage could occur. Install the external regulator with the vent pointing down as
shown in Figure 13. Pointing the vent down protects it from freezing rain or sleet.
NOTICE
A qualified service person must connect heater to gas supply.
Follow all local codes.
WARNING ICON G001
CAUTION
Never connect heater directly to the propane supply. This heater
requires an external regulator (not supplied). Install the external
regulator between the heater and propane supply.
Typical Inlet Pipe Diameters
VP2000BTC 3/8" or greater
VP2800BTC 1/2" or greater
Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream
from heater (see Figure 14, page 15).
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING ICON G001
CAUTION
Use only new, black iron or steel pipe. Internally-tinned copper
tubing may be used in certain areas. Check your local codes. Use
pipe of large enough diameter to allow proper gas volume to heater.
If pipe is too small, undue loss of pressure will occur.
Install sediment trap in supply line as shown in Figure 14, page 15. Locate sediment
trap where it is within reach for cleaning. Locate sediment trap where trapped
matter is not likely to freeze. A sediment trap traps moisture and contaminants. This
keeps them from going into heater controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
WARNING ICON G001
CAUTION
Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Propane
Supply Tank
Vent Pointing
Down
External
Regulator
Figure 13 - External Regulator With Vent Pointing Down