4
1. Keep the chimney connection as short as possible.
The heater must have its own chimney flue. Do not
connect any other appliance to the same flue. If there
is no chimney where you wish to place the heater, you
can use a UL Listed Type 103 HT, Solid Fuel, Factory
Built Chimney. (Figure 7)
2. Place the heater on solid masonry or solid concrete.
When the heater is used on a combustible floor, use a
non-combustible floor protector having a thermal con
ductivity of K=0.45 BTU in./ft. 2 hr.deg. F. with 28
gauge sheet metal or a UL Listed Floor Protector.
Have the floor protector with the specified dimensions.
(See Figure 2.)
3. Check Figures 2, 3, & 4. You should have at least the
clearances shown from the heater and the connector
pipe to combustible surfaces. If you have a solid brick
or stone wall behind your heater, you can place the
heater as close as you wish to the wall. If the wall is only
faced with brick or stone, treat it as a combustible wall.
LOCALOCA
LOCALOCA
LOCA
TING TING
TING TING
TING
THE RTHE R
THE RTHE R
THE R
OOM HEAOOM HEA
OOM HEAOOM HEA
OOM HEA
TERTER
TERTER
TER
AS A LOCATION IS SELECTED, KEEP THE FOLLOWING IN MIND:AS A LOCATION IS SELECTED, KEEP THE FOLLOWING IN MIND:
AS A LOCATION IS SELECTED, KEEP THE FOLLOWING IN MIND:AS A LOCATION IS SELECTED, KEEP THE FOLLOWING IN MIND:
AS A LOCATION IS SELECTED, KEEP THE FOLLOWING IN MIND:
MINIMUM CLEARANCE MINIMUM CLEARANCE
MINIMUM CLEARANCE MINIMUM CLEARANCE
MINIMUM CLEARANCE
TT
TT
T
O COMBO COMB
O COMBO COMB
O COMB
USTIBLE USTIBLE
USTIBLE USTIBLE
USTIBLE
WW
WW
W
ALLSALLS
ALLSALLS
ALLS
FRONT VIEW
Fig. 3
SIDE VIEW
Fig. 4
TOP VIEW
Fig. 2
CAUTION
KEEP FURNISHINGS
AND OTHER COM-
BUSTIBLE MATERIALS
AWAY FROM THE
HEATER
MINIMUM CLEARANCES FOR
CORNERCORNER
CORNERCORNER
CORNER
INSTALLATIONINSTALLATION
INSTALLATIONINSTALLATION
INSTALLATION IS
18 INCHES18 INCHES
18 INCHES18 INCHES
18 INCHES FROM THE
CORNERS OF THE HEATER TO THE NEAREST
WALL
24
26
26
24