Trane WC-IOM-7 Heat Pump User Manual


 
10 Packaged Heat Pump • WC-IOM-7
General Information
Lead/Lag Control (Dual Circuit Only)
Lead/Lag is a selectable input located on the RTRM. The RTRM is configured from
the factory with the Lead/Lag control disabled. To activate the Lead/Lag function,
simply cut the wire connected to J3-8 at the RTRM. When it is activated, each
time the designated lead compressor is shut off due to the load being satisfied,
the lead compressor or refrigeration circuit switches. When the RTRM is powered
up, i.e. after a power failure, the control will default to the number one circuit
compressor.
Zone Sensor Module (ZSM) (BAYSENS007B)
This electronic sensor features three system switch settings (Heat, Cool, and Off)
and two fan settings (On and Auto). It is a manual changeover control with single
setpoint. (Cooling Setpoint Only)
Zone Sensor Module (ZSM) (BAYSENS009B)
This electronic sensor features four system switch settings (Heat, Cool, Auto, and
Off) and two fan settings (On and Auto). It is a manual or auto changeover control
with dual setpoint capability. It can be used with a remote zone temperature
sensor BAYSENS017B.
Zone Sensor (BAYSENS011B)
This electronic sensor features four system switch settings (Heat, Cool, Auto, and
Off) and two fan settings (On and Auto) with four system status LED’s. It is a
manual or auto changeover control with dual setpoint capability. It can be used
with a remote zone temperature sensor BAYSENS017B.
Programmable Zone Sensor - BAYSENS019B
This 7 day programmable sensor features 2, 3 or 4 periods for Occupied or
Unoccupied programming per day. If the power is interrupted, the program is
retained in permanent memory. If power is off for an extended period of time,
only the clock and day may have to be reset.
The Zone Sensor allows selection of 2, 3 or 4 system modes (Heat, Cool, Auto,
and Off), two fan modes (On and Auto). It has dual temperature selection with
programmable start time capability.
The occupied cooling set point ranges between 45 and 98 degrees Fahrenheit.
The heating set point ranges between 43 and 96 degrees Fahrenheit.
A liquid crystal display (LCD) displays zone temperature, temperature set points,
day of the week, time, and operational mode symbols.
The Option Menu is used to enable or disable applicable functions, i.e.; Morning
Warm-up, Economizer minimum position override during unoccupied status,
Fahrenheit or Centigrade, Supply air tempering, Remote zone temperature
sensor, 12/24 hour time display, Smart fan, and Computed recovery.