4
VAV-SVN01E-EN
Service Model
Number Description
WARNING
WARNING
Fiberglass Wool!
WARNING: ALL INSULATED UNITS
(except closed-cell foam insulation)
CONTAIN FIBERGLASS WOOL! Read
this literature prior to installation for
proper instruction. Disturbing the
insulation in this product during
installation, maintenance or repair will
expose you to airborne particles of
glass wool fibers and ceramic fibers
known to the state of California to
cause cancer through inhalation. Glass
wool fibers may also cause respiratory,
skin or eye irritation.
Single-Duct Units
Digit 1, 2—Unit Type
VC VariTrane single-duct
Digit 3—Reheat
C Cooling Only
E Electric Heat
W Hot Water Heat
Digit 4—Development Sequence
F Sixth
Digit 5, 6—Primary Air Valve
04 4" inlet (225 cfm)
05 5" inlet (350 cfm)
06 6" inlet (500 cfm)
08 8" inlet (900 cfm)
10 10" inlet (1400 cfm)
12 12" inlet (2000 cfm)
14 14" inlet (3000 cfm)
16 16" inlet (4000 cfm)
24 24" x 16" inlet (8000 cfm)
Digit 7, 8—Not Used
00 N/A
Digit 9—Not Used
0 N/A
Digit 10, 11—Design Sequence
H0 Fourth (factory assigned)
Digit 12, 13, 14, 15—Controls
ENON No controls, field-installed
DDC/electric
PNON No controls, field-installed
pneumatic
DD00 Trane elec actuator only
DD01 DDC – Cooling only
DD02 DDC – N.C. on/off water valve
control
DD03 DDC – Prop hot water valve
control
DD04 DDC – On/off electric heat
DD05 DDC – Pulse-width modulation
electric heat
DD07 DDC – N.O. on/off water valve
control
DD11 LonTalk DDC Controller—
Cooling only
DD12 LonTalk DDC Controller w/ N.C.
on/off hot water control
DD13 LonTalk DDC Controller w/
proportional hot water control
DD14 LonTalk DDC Controller–on/off
electric heat control
DD15 LonTalk DDC Controller w/
pulse-width modulation electric
heat control
DD17 LonTalk DDC Controller w/ N.O.
on/off hot water control
FM00 FM – Customer-supplied
actuator & controller
FM01 FM – Trane actuator w/ cusomer-
supplied control
VMA1 FM – Johnson controls VMA-1410
VMA2 FM – Johnson controls VMA-1420
PWR1 FM – Seimens 540-100 w/
GDE131.1P actuator
PWR4 FM – Seimens 540-100 w/ Trane
actuator
PWR5 FM – Seimens 540-100 w/
GDE131.1U actuator
AT01 FM – Automated Logic U341V+
AT02 FM – Automated Logic U141V+
EI05 Analog – With optional on/off
reheat
EI28 Analog – With optional on/off
reheat with dual-minimum cfm
EI29 Analog – With optional on/off
reheat with constant-volume cfm
PC00 PN – N.C. Trane pneumatic
actuator
PC04 PN – N.C. with optional on/off HW,
DA Stat
PC05 PN – N.C. with optional on/off
electric, RA Stat
PN00 PN – N.O. Trane pneumatic
actuator, RA Stat
PN04 PN – N.O. PVR, DA Stat
PN05 PN – N.O. PVR, RA Stat
PN11 PN – N.O. dual-minimum cfm,
DA Stat
PN32 PN – Water Valve, N.O. constant
volume, DA Stat
PN34 PN – Electric heat, N.O. constant
volume, DA Stat
Notes
:
N.C. = Normally-closed
N.O. = Normally-opened
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic
t-stat (by others)
PN = Pneumatic
FM = Factory installation of customer-
supplied controller
PVR = Pneumatic Volume Regulator
Digit 16—Insulation
A 1/2" Matte-faced
B 1" Matte-faced
C 1/2" Foil-faced
D 1" Foil-faced
F 1" Double-wall
G 3/8" Closed-cell