12 UNT-SVX07A-EN
Installation
dimensions
& weights
Horizontal Concealed Unit Dimensions, in-lbs.
unit
size 02-03 04 06 08 10-12
A 2’-8
11
/16” 3’-1
11
/16” 3’-11
3
/16” 4’-7
11
/16” 6’-2
11
/16”
B 1’-9
5
/16” 2’-2
5
/16” 2’-11
13
/16” 3’-8
5
/16” 5’-3
5
/16”
C 1’-10
13
/16” 2’-3
13
/16” 3’-1
5
/16” 3’-9
13
/16” 5’-4
13
/16”
D 1’-7
3
/8” 2’-0
3
/8” 2’-9
7
/8” 3’-6
3
/8” 5’-1
3
/8”
E 1’-6
1
/8” 1’-11
1
/8” 2’-8
5
/8” 3’-5
1
/8” 5’-0
1
/8”
F 1’-7
5
/16” 2’-0
5
/16” 2’-9
13
/16” 3’-6
5
/16” 5’-1
5
/16”
operating weight 81 109 139 147 200
shipping weight 68 96 123 131 182
Notes:
1. Coil connections are always on the drain pan side and opposite the control
box.
2. Coil connections are
5
/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
Horizontal Concealed, Model C