Table EP-4 Electric Power — Model P Unit Heater — Motor
Accessory
Model Motor Operating MAX
Number Type Voltage AMP MCA FUSE HP RPM
42 Totally Enclosed 115/60/1 1.23** 1.6 15 1/40* 1550
64,80 Totally Enclosed 115/60/1 2.1 2.6 15 1/20* 1550
102 Totally Enclosed 115/60/1 1.2** 1.5 15 1/8* 1070
122,146,166 Totally Enclosed 115/60/1 2.3** 2.9 15 1/6 1100
202 Totally Enclosed 115/60/1 3.6** 4.5 15 1/4 1100
252 Totally Enclosed 115/60/1 3.6** 4.5 15 1/4 1100
280 Totally Enclosed 115/60/1 5.4** 6.8 15 1/2 1100
42 Totally Enclosed 208-230/460/60/3 0.98-1.1/0.55 1.2-1.4/0.7 15-15/15 1/6 1140
64,80 Totally Enclosed 208-230/460/60/3 0.98-1.1/0.55 1.2-1.4/0.7 15-15/15 1/6 1140
102 Totally Enclosed 208-230/460/60/3 0.98-1.1/0.55 1.2-1.4/0.7 15-15/15 1/6 1140
122,146,166 Totally Enclosed 208-230/460/60/3 0.98-1.1/0.55 1.2-1.4/0.7 15-15/15 1/6 1140
202 Totally Enclosed 208-230/460/60/3 1.2-1.4/0.7 1.5-1.8/0.9 15-15/15 1/4 1140
252 Totally Enclosed 208-230/460/60/3 1.2-1.4/0.7 1.5-1.8/0.9 15-15/15 1/4 1140
280 Totally Enclosed 208-230/460/60/3 1.8-2.0/1.0 2.3-2.5/1.3 15-15/15 1/2 1140
336,384 Totally Enclosed 208-230/460/60/3 3.1-3.2/1.6 3.9-4.0/2.0 15-15/15 3/4 1140
500,600 Totally Enclosed 208-230/460/60/3 5.3-5.0/2.5 6.6-6.3/3.1 15-15/15 1-½ 11 6 0
720 Totally Enclosed 208-230/460/60/3 9.9-9.8/4.9 12.4-12.3/6.1 20-20/15 3 1165
*Optional variable speed switch is available.
**These motors have automatic thermal overload protection or impedance protection.
CAUTION: Select appropriate AMP, MCA, and MAX FUSE for the multiple voltage motors. For example, the AMP, MCA, and MAX FUSE for Model 720 with a 230 volt Totally Enclosed motor
is 9.8, 12.3, and 20 respectively.
Accessory
Model Motor Operating MAX
Number Type Voltage AMP MCA FUSE HP RPM
Explosion Proof
42 with Thermal Overload 115/60/1 3.8 4.8 15 1/6 1140
Explosion Proof
64,80 with Thermal Overload 115/60/1 3.8 4.8 15 1/6 1140
Explosion Proof
102 with Thermal Overload 115/60/1 3.8 4.8 15 1/6 1140
Explosion Proof
122,146,166 with Thermal Overload 115/60/1 3.8 4.8 15 1/6 1140
Explosion Proof
202 with Thermal Overload 115/60/1 4.4 5.5 15 1/4 1140
Explosion Proof
252 with Thermal Overload 115/60/1 4.4 5.5 15 1/4 1140
Explosion Proof
280 with Thermal Overload 115/60/1 7.8 9.8 20 1/2 1140
Explosion Proof
42 with Thermal Overload 208-230/460/60/3 1.0-1.0/0.5 1.3-1.3/0.6 15-15/15 1/6 1140
Explosion Proof
64,80 with Thermal Overload 208-230/460/60/3 1.0-1.0/0.5 1.3-1.3/0.6 15-15/15 1/6 1140
Table EP-5 Electric Power — Model P Unit Heater — Motor