Trane TTA075A-TTA200B Fan User Manual


 
26 SS-PRC003-EN
Performance
Data System
Table PD-14 Gross Cooling Capacities (MBh) - Single Compressor - TTA155C Condensing Unit with TWE155B Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 90.4 90.4 99.1 67.0 109.4 42.8 87.8 87.8 95.6 65.6 105.2 41.5 84.6 84.6 91.5 64.0 100.7 40.0 80.9 80.9 87.0 62.2 95.7 38.3
80 96.3 96.3 99.6 87.3 109.8 62.7 93.4 93.4 96.1 85.9 105.5 61.1 90.1 90.1 92.1 84.3 101.1 59.5 86.2 86.2 87.6 82.5 96.1 57.7
4500
85 102.2 102.2 102.3 102.3 109.9 82.7 99.2 99.2 99.3 99.3 106.0 81.3 95.7 95.7 95.8 95.8 101.5 79.7 91.7 91.7 91.8 91.8 96.5 77.9
90 108.3 108.3 108.4 108.4 110.7 103.2 105.1 105.1 105.2 105.2 106.9 101.8 101.4 101.4 101.5 101.5 102.6 100.3 97.3 97.3 97.4 97.4 97.5 97.5
75 92.5 92.5 100.2 70.1 110.4 42.7 89.7 89.7 96.6 68.6 106.2 41.3 86.4 86.4 92.4 67.0 101.5 39.8 82.6 82.6 87.8 65.1 96.5 38.1
80 98.6 98.6 100.8 92.2 110.6 65.1 95.6 95.6 97.3 90.8 106.6 63.6 92.1 92.1 93.3 89.2 102.0 62.0 88.1 88.1 88.8 87.4 97.0 60.3
5000
85 104.7 104.7 104.8 104.8 111.1 87.2 101.6 101.6 101.7 101.7 107.0 85.7 97.9 97.9 98.0 98.0 102.5 84.1 93.8 93.8 93.9 93.9 97.5 82.4
90 111.0 111.0 111.1 111.1 112.2 109.7 107.6 107.6 107.7 107.7 108.4 108.3 103.8 103.8 103.9 103.9 104.0 104.0 99.6 99.6 99.7 99.7 99.8 99.8
75 94.4 94.4 101.1 72.9 111.3 43.5 91.5 91.5 97.5 71.5 107.0 42.1 88.0 88.0 93.2 69.8 102.3 40.6 84.1 84.1 88.5 68.0 97.1 38.9
80 100.6 100.6 102.0 97.0 111.5 67.6 97.5 97.5 98.4 95.6 107.4 66.1 93.8 93.8 94.4 94.0 102.8 64.5 89.7 89.7 89.8 89.8 97.8 62.7
5500
85 106.9 106.9 107.0 107.0 112.0 91.5 103.6 103.6 103.7 103.7 107.9 90.1 99.8 99.8 99.9 99.9 103.3 88.5 95.6 95.6 95.6 95.6 98.3 86.7
90 113.2 113.2 113.4 113.4 113.4 113.4 109.8 109.8 109.9 109.9 110.0 110.0 105.9 105.9 106.0 106.0 106.0 106.0 101.5 101.5 101.6 101.6 101.7 101.7
75 96.0 96.0 101.9 75.7 112.0 44.3 92.9 92.9 98.2 74.3 107.6 42.9 89.4 89.4 93.9 72.6 102.9 41.3 85.4 85.4 89.1 70.7 97.6 39.7
80 102.3 102.3 103.0 101.7 112.4 70.7 99.1 99.1 99.1 99.1 108.2 68.5 95.3 95.3 95.4 95.4 103.5 66.8 91.1 91.1 91.2 91.2 98.4 65.1
6000
85 108.7 108.7 108.8 108.8 112.8 95.7 105.3 105.3 105.4 105.4 108.7 94.3 101.4 101.4 101.5 101.5 104.1 92.6 97.1 97.1 97.2 97.2 99.1 90.9
90 115.1 115.1 115.2 115.2 115.3 115.3 111.7 111.7 111.8 111.8 111.9 111.9 107.6 107.6 107.7 107.7 107.8 107.8 103.2 103.2 103.3 103.3 103.4 103.4
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-14 Gross Cooling Capacities (kW) - Single Compressor - TTA155C Condensing Unit with TWE155B Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 26.5 26.5 29.0 19.6 32.0 12.5 25.7 25.7 28.0 19.2 30.8 12.1 24.8 24.8 26.8 18.7 29.5 11.7 23.7 23.7 25.5 18.2 28.0 11.2
27 28.2 28.2 29.2 25.6 32.1 18.4 27.4 27.4 28.1 25.2 30.9 17.9 26.4 26.4 27.0 24.7 29.6 17.4 25.2 25.2 25.7 24.2 28.2 16.9
7646
29 29.9 29.9 30.0 30.0 32.2 24.2 29.1 29.1 29.1 29.1 31.0 23.8 28.0 28.0 28.0 28.0 29.7 23.3 26.9 26.9 26.9 26.9 28.3 22.8
32 31.7 31.7 31.7 31.7 32.4 30.2 30.8 30.8 30.8 30.8 31.3 29.8 29.7 29.7 29.7 29.7 30.0 29.4 28.5 28.5 28.5 28.5 28.6 28.6
24 27.1 27.1 29.3 20.5 32.3 12.5 26.3 26.3 28.3 20.1 31.1 12.1 25.3 25.3 27.1 19.6 29.7 11.6 24.2 24.2 25.7 19.1 28.2 11.2
27 28.9 28.9 29.5 27.0 32.4 19.1 28.0 28.0 28.5 26.6 31.2 18.6 27.0 27.0 27.3 26.1 29.9 18.2 25.8 25.8 26.0 25.6 28.4 17.6
8496
29 30.7 30.7 30.7 30.7 32.5 25.5 29.7 29.7 29.8 29.8 31.3 25.1 28.7 28.7 28.7 28.7 30.0 24.6 27.5 27.5 27.5 27.5 28.5 24.1
32 32.5 32.5 32.5 32.5 32.9 32.1 31.5 31.5 31.5 31.5 31.7 31.7 30.4 30.4 30.4 30.4 30.5 30.5 29.2 29.2 29.2 29.2 29.2 29.2
24 27.6 27.6 29.6 21.4 32.6 12.7 26.8 26.8 28.5 20.9 31.3 12.3 25.8 25.8 27.3 20.4 29.9 11.9 24.6 24.6 25.9 19.9 28.4 11.4
27 29.4 29.4 29.9 28.4 32.7 19.8 28.5 28.5 28.8 28.0 31.5 19.4 27.5 27.5 27.6 27.5 30.1 18.9 26.3 26.3 26.3 26.3 28.6 18.4
9346
29 31.3 31.3 31.3 31.3 32.8 26.8 30.3 30.3 30.4 30.4 31.6 26.4 29.2 29.2 29.2 29.2 30.3 25.9 28.0 28.0 28.0 28.0 28.8 25.4
32 33.2 33.2 33.2 33.2 33.2 33.2 32.1 32.1 32.2 32.2 32.2 32.2 31.0 31.0 31.0 31.0 31.0 31.0 29.7 29.7 29.8 29.8 29.8 29.8
24 28.1 28.1 29.8 22.2 32.8 13.0 27.2 27.2 28.7 21.7 31.5 12.5 26.2 26.2 27.5 21.3 30.1 12.1 25.0 25.0 26.1 20.7 28.6 11.6
27 30.0 30.0 30.2 29.8 32.9 20.7 29.0 29.0 29.0 29.0 31.7 20.1 27.9 27.9 27.9 27.9 30.3 19.6 26.7 26.7 26.7 26.7 28.8 19.0
10195
29 31.8 31.8 31.9 31.9 33.0 28.0 30.8 30.8 30.9 30.9 31.8 27.6 29.7 29.7 29.7 29.7 30.5 27.1 28.4 28.4 28.5 28.5 29.0 26.6
32 33.7 33.7 33.7 33.7 33.8 33.8 32.7 32.7 32.7 32.7 32.8 32.8 31.5 31.5 31.5 31.5 31.6 31.6 30.2 30.2 30.2 30.2 30.3 30.3
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity