16 SS-PRC003-EN
Performance
Data System
Table PD-4 — Gross Cooling Capacities (MBh) TTA085A Condensing Unit with TWE100A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 87.9 67.0 97.4 57.4 107.7 39.8 84.8 65.4 93.9 56.0 103.9 38.3 81.5 63.7 90.3 54.5 99.8 36.8 78.0 61.9 86.5 53.0 95.4 35.5
80 88.3 77.4 97.8 65.0 107.9 51.3 85.2 75.8 94.4 63.4 104.1 49.8 81.9 74.1 90.8 61.9 100.2 48.3 78.5 72.3 86.7 59.9 96.0 46.7
2500
85 89.3 88.1 98.0 75.3 108.3 62.2 86.1 86.1 94.6 73.7 104.6 60.7 83.4 83.4 91.0 72.0 100.7 59.2 80.6 80.6 87.3 70.2 96.6 57.6
90 93.2 93.2 98.3 85.7 108.7 73.0 90.6 90.6 95.0 84.1 104.9 71.5 87.9 87.9 91.4 82.4 100.8 69.6 85.0 85.0 87.8 80.7 96.8 67.9
75 90.0 70.2 99.6 56.2 109.9 40.6 86.8 68.5 96.0 54.6 105.8 39.2 83.4 66.8 92.3 53.0 101.5 37.7 79.8 64.9 88.3 51.4 97.0 36.1
80 90.5 81.6 100.1 68.1 110.2 53.1 87.3 80.0 96.5 66.5 106.3 51.6 83.9 78.2 92.5 64.5 102.2 50.0 80.5 76.4 88.6 62.7 97.9 48.4
2800
85 92.0 92.0 100.3 79.2 110.7 65.0 89.4 89.4 96.7 77.5 106.8 63.5 86.6 86.6 93.0 75.8 102.7 62.0 83.6 83.6 89.2 74.1 98.5 60.4
90 96.8 96.8 100.7 90.7 110.8 76.5 94.1 94.1 97.2 89.0 106.9 74.9 91.2 91.2 93.6 87.4 102.9 73.2 88.2 88.2 89.9 85.6 98.7 71.5
75 91.8 73.2 101.5 58.1 111.6 41.4 88.5 71.5 97.7 56.5 107.3 40.0 85.0 69.7 93.9 54.9 102.9 38.5 81.3 67.8 89.8 53.2 98.3 36.9
80 92.4 85.7 101.7 70.6 112.1 54.7 89.2 84.0 98.0 68.9 108.0 53.2 85.7 82.2 94.2 67.1 103.8 51.6 82.2 80.4 90.2 65.3 99.4 50.0
3100
85 95.0 95.0 102.2 82.9 112.7 67.7 92.2 92.2 98.6 81.3 108.6 66.2 89.3 89.3 94.7 79.5 104.4 64.6 86.2 86.2 90.8 77.7 99.7 62.5
90 100.0 100.0 102.8 95.4 112.9 80.0 97.2 97.2 99.3 93.8 108.9 78.3 94.1 94.1 95.6 92.1 104.7 76.6 91.0 91.0 91.9 90.4 100.4 74.9
75 93.4 76.1 103.0 59.9 113.0 42.2 89.9 74.3 99.2 58.3 108.6 40.7 86.3 72.5 95.2 56.7 104.1 39.1 82.5 70.6 91.1 55.0 99.4 37.4
80 94.1 89.6 103.3 73.2 113.7 56.3 90.8 87.9 99.5 71.4 109.5 54.8 87.4 86.1 95.6 69.7 105.2 53.2 83.6 83.6 91.5 67.8 100.7 51.6
3400
85 97.7 97.7 103.9 86.5 114.3 70.3 94.8 94.8 100.1 84.8 110.2 68.7 91.7 91.7 96.2 83.0 105.5 66.6 88.5 88.5 92.1 81.2 101.1 64.8
90 102.9 102.9 104.7 100.1 114.6 83.3 99.9 99.9 101.1 98.4 110.5 81.6 96.7 96.7 97.5 96.7 106.2 79.9 93.4 93.4 93.5 93.5 101.8 78.1
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-4 — Gross Cooling Capacities (kW) TTA085A Condensing Unit with TWE100A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 25.7 19.6 28.5 16.8 31.5 11.6 24.8 19.1 27.5 16.4 30.4 11.2 23.9 18.6 26.4 16.0 29.2 10.8 22.8 18.1 25.3 15.5 27.9 10.4
27 25.9 22.7 28.6 19.0 31.6 15.0 24.9 22.2 27.6 18.6 30.5 14.6 24.0 21.7 26.6 18.1 29.3 14.1 23.0 21.2 25.4 17.5 28.1 13.7
4248
29 26.1 25.8 28.7 22.0 31.7 18.2 25.2 25.2 27.7 21.6 30.6 17.8 24.4 24.4 26.6 21.1 29.5 17.3 23.6 23.6 25.6 20.6 28.3 16.9
32 27.3 27.3 28.8 25.1 31.8 21.4 26.5 26.5 27.8 24.6 30.7 20.9 25.7 25.7 26.8 24.1 29.5 20.4 24.9 24.9 25.7 23.6 28.3 19.9
24 26.4 20.6 29.2 16.4 32.2 11.9 25.4 20.1 28.1 16.0 31.0 11.5 24.4 19.5 27.0 15.5 29.7 11.0 23.4 19.0 25.9 15.0 28.4 10.6
27 26.5 23.9 29.3 19.9 32.3 15.5 25.6 23.4 28.3 19.5 31.1 15.1 24.6 22.9 27.1 18.9 29.9 14.6 23.6 22.4 25.9 18.3 28.7 14.2
4756
29 26.9 26.9 29.4 23.2 32.4 19.0 26.2 26.2 28.3 22.7 31.3 18.6 25.3 25.3 27.2 22.2 30.1 18.1 24.5 24.5 26.1 21.7 28.8 17.7
32 28.4 28.4 29.5 26.5 32.4 22.4 27.6 27.6 28.5 26.1 31.3 21.9 26.7 26.7 27.4 25.6 30.1 21.4 25.8 25.8 26.3 25.1 28.9 20.9
24 26.9 21.4 29.7 17.0 32.7 12.1 25.9 20.9 28.6 16.6 31.4 11.7 24.9 20.4 27.5 16.1 30.1 11.3 23.8 19.9 26.3 15.6 28.8 10.8
27 27.1 25.1 29.8 20.7 32.8 16.0 26.1 24.6 28.7 20.2 31.6 15.6 25.1 24.1 27.6 19.7 30.4 15.1 24.1 23.6 26.4 19.1 29.1 14.7
5267
29 27.8 27.8 29.9 24.3 33.0 19.8 27.0 27.0 28.9 23.8 31.8 19.4 26.1 26.1 27.7 23.3 30.6 18.9 25.2 25.2 26.6 22.8 29.2 18.3
32 29.3 29.3 30.1 27.9 33.0 23.4 28.4 28.4 29.1 27.5 31.9 22.9 27.6 27.6 28.0 27.0 30.7 22.4 26.6 26.6 26.9 26.5 29.4 21.9
24 27.3 22.3 30.2 17.5 33.1 12.4 26.3 21.8 29.0 17.1 31.8 11.9 25.3 21.2 27.9 16.6 30.5 11.4 24.2 20.7 26.7 16.1 29.1 11.0
27 27.6 26.2 30.2 21.4 33.3 16.5 26.6 25.7 29.1 20.9 32.1 16.0 25.6 25.2 28.0 20.4 30.8 15.6 24.5 24.5 26.8 19.9 29.5 15.1
5778
29 28.6 28.6 30.4 25.3 33.5 20.6 27.8 27.8 29.3 24.8 32.3 20.1 26.9 26.9 28.2 24.3 30.9 19.5 25.9 25.9 27.0 23.8 29.6 19.0
32 30.1 30.1 30.7 29.3 33.6 24.4 29.2 29.2 29.6 28.8 32.3 23.9 28.3 28.3 28.5 28.3 31.1 23.4 27.4 27.4 27.4 27.4 29.8 22.9
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity