Trane TRG-TRC010-EN Air Conditioner User Manual


 
TRG-TRC010-EN 33
period four
Maintenance Considerations
notes
Some centrifugal compressor designs do require periodic maintenance of
mechanical system components. This includes oil and refrigerant filter changes,
oil strainer changes, and a compressor inspection.
Open-motor compressor designs require shaft alignment, coupling inspection,
bearing lubrication, and cleaning of the motor windings on a quarterly or
annual basis.
In all cases, strictly follow the maintenance requirements and
recommendations published by the manufacturer.
To ensure optimum heat transfer performance, the heat transfer surfaces must
be kept free of scale and sludge. Even a thin deposit of scale can substantially
reduce heat transfer capacity. Engage the services of a qualified water
treatment specialist to determine the level of water treatment required to
remove contaminants from the cooling tower water.
Other design-specific requirements
Change oil when oil analysis dictates
Replace oil filter periodically
Replace filter drier periodically
Clean oil strainers annually
Check shaft alignment annually
Check coupling annually
Replace shaft seal every 2 to 4 years
Compressor teardown inspection every 5 to 10 years
maintenance considerations
Mechanical Components
Figure 47
maintenance considerations
Heat Transfer Surfaces
Recommended maintenance
Use a qualified water treatment
specialist
Clean condenser tubes as
needed
Clean water-side strainers
Test tubes every 3 years
Figure 48