Maintenance Considerations
notes
Guideline 3, “
Reducing Emission of Halogenated Refrigerants in Refrigeration
and Air Conditioning Equipment and Systems
,” is one of several advisory
documents published by the American Society of Heating, Refrigerating and
Air-Conditioning Engineers (ASHRAE). This guideline includes a list of
recommended data points to be logged daily for each chiller. Much of this data
may be available from the display on the chiller control panel.
Special attention should be given to:
Reviewing the operating log and trends
Observing the oil pressure drop to determine if the oil filter needs to be
replaced
Monitoring evaporator and condenser approach temperatures
Observing and recording the oil level
Monitoring purge pump-out operation
operating log
ASHRAE Guideline 3
Chilled water inlet and outlet
temperatures and pressures
Chilled water flow
Evaporator refrigerant
temperature and pressures
Evaporator approach
temperature
Condenser water inlet and
outlet temperatures and
pressures
Condenser water flow
Condenser refrigerant
temperature and pressures
Condenser approach
temperature
Oil pressures, temperature, and
levels
Addition of refrigerant
Addition of oil
Vibration levels
Figure 45