8 Pub. No. 22-1847-03
TAM7A0B30 AIRFLOW PERFORMANCE
CONSTANT CFM MODE / CONSTANT TORQUE MODE
OUTDOOR
MULTIPLIER
(TONS)
COOLING
AIRFLOW
SETTING
Airow
Power
EXTERNAL STATIC PRESSURE
HEATING
AIRFLOW
SETTING
Airow
Power
EXTERNAL STATIC PRESSURE
0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9
1.5 tons
360
CFM/ton
CFM
Watts
591 / 685
30 / 41
560 / 538
58 / 56
533 / 299
87 / 63
509 / NA
118 / NA
482 / NA
150 / NA
390
CFM/ton
CFM
Watts
630
35
609
65
588
96
566
128
540
161
380
CFM/ton
CFM
Watts
618 / 711
33 / 45
593 / 572
62 / 60
569 / 359
93 / 68
547 / NA
125 / NA
524 / NA
158 / NA
410
CFM/ton
CFM
Watts
657
38
639
70
621
102
601
136
578
169
400
CFM/ton
CFM
Watts
645 / 738
37 / 49
624 / 605
67 / 65
604 / 410
99 / 73
584 / NA
132 / NA
562 / NA
166 / NA
430
CFM/ton
CFM
Watts
683
42
669
75
653
109
636
143
614
177
420
CFM/ton
CFM
Watts
659 / 751
38 / 50
639 / 621
69 / 67
620 / 434
102 / 76
602 / NA
136 / NA
581 / NA
170 / NA
450
CFM/ton
CFM
Watts
709
45
698
80
685
115
669
151
649
186
2 tons †
360
CFM/ton
CFM
Watts
750 / 840
51 / 66
741 / 726
87 / 85
731 / 575
125 / 96
719 / 344
163 / 99
704 / NA
200 / NA
390
CFM/ton
CFM
Watts
800
60
797
99
791
139
781
180
766
219
380
CFM/ton
CFM
Watts
784 / 874
57 / 72
779 / 764
95 / 92
771 / 622
134 / 104
762 / 419
174 / 107
748 / NA
213 / NA
410
CFM/ton
CFM
Watts
834
66
834
107
830
150
822
192
810
233
400 †
CFM/ton
CFM
Watts
818 / 908
62 / 79
816 / 802
103 / 100
811 / 667
144 / 113
803 / 484
186 / 117
792 / NA
227 / NA
430
CFM/ton
CFM
Watts
868
73
871
116
869
161
864
205
853
248
420
CFM/ton
CFM
Watts
835 / 924
66 / 83
834 / 820
107 / 104
831 / 689
150 / 118
824 / 513
192 / 122
813 / 180
234 / 132
450
CFM/ton
CFM
Watts
902
80
908
126
908
172
905
219
895
263
2.5 tons
360
CFM/ton
CFM
Watts
904 / 1017
80 / 105
908 / 921
125 / 129
909 / 804
172 / 144
907 / 658
219 / 150
898 / 454
264 / 148
390
CFM/ton
CFM
Watts
967
95
977
145
982
196
982
247
974
295
380
CFM/ton
CFM
Watts
947 / 1061
89 / 117
955 / 968
138 / 142
959 / 856
188 / 158
958 / 718
237 / 165
951 / 538
285 / 163
410
CFM/ton
CFM
Watts
1012
106
1025
160
1033
214
1034
268
1027
318
400
CFM/ton
CFM
Watts
991 / 1106
100 / 131
1002 / 1016
152 / 156
1009 / 908
205 / 174
1010 / 779
257 / 182
1003 / 614
307 / 180
430
CFM/ton
CFM
Watts
1057
119
1074
176
1084
234
1087
290
1078
342
420
CFM/ton
CFM
Watts
1013 / 1129
106 / 138
1026 / 1040
159 / 164
1034 / 934
214 / 182
1036 / 808
268 / 190
1029 / 650
318 / 189
450
CFM/ton
CFM
Watts
1104
133
1124
194
1136
255
1139
314
1128
366
3 tons
360
CFM/ton
CFM
Watts
1063 / 1182
120 / 156
1080 / 1095
177 / 182
1091 / 993
236 / 201
1094 / 873
292 / 211
1085 / 727
344 / 210
390
CFM/ton
CFM
Watts
1147
147
1170
211
1184
276
1185
336
1170
389
380
CFM/ton
CFM
Watts
1120 / 1241
137 / 178
1140 / 1157
199 / 205
1153 / 1059
262 / 225
1156 / 945
321 / 235
1444 / 809
374 / 236
410
CFM/ton
CFM
Watts
1208
168
1233
238
1247
306
1245
367
1223
418
400
CFM/ton
CFM
Watts
1179 / 1304
157 / 203
1202 / 1221
224 / 231
1216 / 1127
290 / 252
1216 / 1018
351 / 263
1198 / 890
403 / 265
430
CFM/ton
CFM
Watts
1271
193
1298
267
1309
337
1300
398
1271
446
420
CFM/ton
CFM
Watts
1210 / 1337
168 / 217
1233 / 1255
237 / 246
1247 / 1162
305 / 267
1245 / 1055
306 / 279
1224 / 931
417 / 281
450
CFM/ton
CFM
Watts
1338
221
1363
299
1368
369
1350
427
1314
472
NOTES:
1. † Factory Setting
2. Status LED will blink once per 100 CFM requested. In torque mode, actual airow may be lower.
3. Torque mode will reduce airow when static is above approximately
0.35" water column.
4. All heating modes default to Constant CFM
5. Cooling airow values are with wet coil, no lter
Minimum Heating Airow Settings
NOTE: Minimum auxiliary heating airow is automatically congured by the air handler model and
the auxiliary heater model number. This is not eld adjustable.
MODEL NO.
BAYEVAC05BK1A
A
BAYEVAC05LG1AA
BAYEVAC08BK1A
A
BAYEVAC08LG1AA
BAYEVAC10BK1A
A
BAYEVAC10LG1AA
BAYEVAC10LG3AA
BAYEVCB15LG3AA BAYEVBC15BK1AA
BAYEVBC20BK1AA
TAM7A0B30H21S
B
723/80
8
723/102
0
765/102
0
680/80
8
765/106
3
850/110
5
--
MINIMUM HEATER AIRFLOW CFM - HEATER MATRI
X
WITHOUT HEAT PUMP / WITH HP
SEE AIR HANDLER NAMEPLATE FOR APPROVED COMBINATIONS