Trane SS-PRC003-EN Fan User Manual


 
19SS-PRC003-EN
Performance
Data System
Table PD-7 Gross Cooling Capacities (MBh) - Both Compressors - TTA100C Condensing Unit with TWE100A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 99.7 78.1 110.4 66.8 121.8 45.0 95.7 76.1 106.1 65.1 117.1 43.3 91.5 74.0 101.4 63.3 112.1 41.6 87.0 71.7 96.5 61.4 106.8 39.8
80 100.2 90.9 110.7 75.3 121.9 58.6 96.3 88.9 106.4 73.5 117.2 56.8 92.2 86.8 101.8 71.5 112.3 54.9 87.9 84.7 97.0 69.4 107.0 52.9
3000
85 102.1 102.1 110.9 88.1 122.2 71.8 98.8 98.8 106.6 86.1 117.5 70.0 95.3 95.3 102.0 84.1 112.6 68.1 91.6 91.6 97.2 81.9 107.4 66.1
90 107.3 107.3 111.4 100.9 122.4 85.0 104.0 104.0 107.2 99.0 117.7 83.2 100.4 100.4 102.8 97.0 112.7 81.0 96.6 96.6 98.2 94.9 107.5 79.0
75 101.7 81.6 112.5 64.3 123.9 45.8 97.6 79.5 108.1 62.4 119.0 44.1 93.2 77.3 103.3 60.4 113.8 42.3 88.6 75.1 98.2 58.3 108.4 40.3
80 102.4 95.6 112.8 78.7 124.0 60.4 98.4 93.6 108.4 76.8 119.1 58.6 94.2 91.5 103.4 74.4 114.0 56.7 89.9 89.3 98.5 72.3 108.6 54.7
3325
85 105.4 105.4 113.0 92.4 124.3 74.8 102.0 102.0 108.6 90.4 119.4 73.0 98.4 98.4 103.9 88.3 114.3 71.1 94.5 94.5 98.9 86.1 109.0 69.1
90 110.9 110.9 113.7 106.4 124.5 89.1 107.4 107.4 109.5 104.5 119.5 86.9 103.7 103.7 105.0 102.5 114.5 84.9 99.7 99.7 99.8 99.8 109.2 82.9
75 103.6 85.1 114.2 73.6 125.6 46.8 99.3 83.0 109.6 71.2 120.6 45.0 94.8 80.8 104.8 69.3 115.3 43.1 90.0 78.5 99.6 67.3 109.7 41.6
80 104.5 100.4 114.5 81.8 125.8 62.3 100.5 98.4 109.9 79.8 120.8 60.4 95.7 95.7 105.1 77.6 115.6 58.5 91.8 91.8 100.0 75.4 110.1 56.5
3650
85 108.6 108.6 114.8 96.8 126.1 77.9 105.0 105.0 110.3 94.8 121.1 76.0 101.2 101.2 105.6 92.7 115.9 74.1 97.2 97.2 100.6 90.5 110.4 72.1
90 114.2 114.2 116.0 112.2 126.3 93.0 110.5 110.5 111.7 110.2 121.3 91.0 106.7 106.7 106.8 106.8 116.1 89.0 102.6 102.6 102.7 102.7 110.7 86.9
75 105.0 88.3 115.7 68.4 127.1 47.3 100.6 86.2 111.1 66.5 121.9 45.4 96.0 83.9 106.1 64.5 116.5 43.4 91.3 81.6 100.8 62.4 110.8 41.5
80 106.3 104.8 115.9 84.6 127.3 64.0 101.8 101.8 111.3 82.6 122.1 62.1 97.9 97.9 106.4 80.5 116.8 60.2 93.8 93.8 101.2 78.2 111.2 58.2
4000
85 111.2 111.2 116.3 100.7 127.6 80.6 107.5 107.5 111.8 98.7 122.5 78.8 103.6 103.6 107.0 96.6 117.2 76.8 99.4 99.4 101.9 94.4 111.4 74.4
90 116.9 116.9 117.9 117.3 127.8 96.6 113.2 113.2 113.3 113.3 122.7 94.7 109.2 109.2 109.2 109.2 117.4 92.6 104.9 104.9 105.0 105.0 111.9 90.5
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-7 Gross Cooling Capacities (kW) - Both Compressors - TTA100C Condensing Unit with TWE100A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 29.2 22.9 32.3 19.6 35.7 13.2 28.0 22.3 31.1 19.1 34.3 12.7 26.8 21.7 29.7 18.5 32.8 12.2 25.5 21.0 28.3 18.0 31.3 11.6
27 29.3 26.6 32.4 22.1 35.7 17.1 28.2 26.0 31.2 21.5 34.3 16.6 27.0 25.4 29.8 20.9 32.9 16.1 25.7 24.8 28.4 20.3 31.3 15.5
5098
29 29.9 29.9 32.5 25.8 35.8 21.0 28.9 28.9 31.2 25.2 34.4 20.5 27.9 27.9 29.9 24.6 33.0 19.9 26.8 26.8 28.5 24.0 31.4 19.4
32 31.4 31.4 32.6 29.6 35.8 24.9 30.5 30.5 31.4 29.0 34.5 24.4 29.4 29.4 30.1 28.4 33.0 23.7 28.3 28.3 28.8 27.8 31.5 23.1
24 29.8 23.9 32.9 18.8 36.3 13.4 28.6 23.3 31.6 18.3 34.8 12.9 27.3 22.6 30.2 17.7 33.3 12.4 25.9 22.0 28.8 17.1 31.7 11.8
27 30.0 28.0 33.0 23.0 36.3 17.7 28.8 27.4 31.7 22.5 34.9 17.2 27.6 26.8 30.3 21.8 33.4 16.6 26.3 26.2 28.8 21.2 31.8 16.0
5648
29 30.9 30.9 33.1 27.0 36.4 21.9 29.9 29.9 31.8 26.5 35.0 21.4 28.8 28.8 30.4 25.9 33.5 20.8 27.7 27.7 29.0 25.2 31.9 20.2
32 32.5 32.5 33.3 31.2 36.5 26.1 31.4 31.4 32.1 30.6 35.0 25.5 30.4 30.4 30.8 30.0 33.5 24.9 29.2 29.2 29.2 29.2 32.0 24.3
24 30.3 24.9 33.4 21.6 36.8 13.7 29.1 24.3 32.1 20.8 35.3 13.2 27.8 23.7 30.7 20.3 33.7 12.6 26.4 23.0 29.2 19.7 32.1 12.2
27 30.6 29.4 33.5 23.9 36.8 18.2 29.4 28.8 32.2 23.4 35.4 17.7 28.0 28.0 30.8 22.7 33.8 17.1 26.9 26.9 29.3 22.1 32.2 16.6
6203
29 31.8 31.8 33.6 28.3 36.9 22.8 30.7 30.7 32.3 27.7 35.5 22.3 29.6 29.6 30.9 27.1 33.9 21.7 28.4 28.4 29.4 26.5 32.3 21.1
32 33.4 33.4 34.0 32.8 37.0 27.2 32.4 32.4 32.7 32.3 35.5 26.7 31.2 31.2 31.3 31.3 34.0 26.1 30.0 30.0 30.1 30.1 32.4 25.4
24 30.7 25.8 33.9 20.0 37.2 13.8 29.5 25.2 32.5 19.5 35.7 13.3 28.1 24.6 31.1 18.9 34.1 12.7 26.7 23.9 29.5 18.3 32.4 12.1
27 31.1 30.7 33.9 24.8 37.3 18.7 29.8 29.8 32.6 24.2 35.8 18.2 28.7 28.7 31.1 23.6 34.2 17.6 27.5 27.5 29.6 22.9 32.6 17.0
6797
29 32.6 32.6 34.1 29.5 37.4 23.6 31.5 31.5 32.7 28.9 35.9 23.1 30.3 30.3 31.3 28.3 34.3 22.5 29.1 29.1 29.8 27.6 32.6 21.8
32 34.2 34.2 34.5 34.3 37.4 28.3 33.1 33.1 33.2 33.2 35.9 27.7 32.0 32.0 32.0 32.0 34.4 27.1 30.7 30.7 30.7 30.7 32.8 26.5
Dry coil conditions. Total Gross Cooling Capacity (kW) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity