17SS-PRC003-EN
Table PD-5 — Gross Cooling Capacities (MBh) TTA100A Condensing Unit with TWE100A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 102.0 77.6 112.8 67.2 124.5 46.0 98.2 75.7 108.7 65.5 119.9 44.4 94.3 73.6 104.4 63.8 115.1 42.7 90.2 71.5 99.9 62.0 110.1 41.0
80 102.4 89.6 113.2 75.1 124.6 59.2 98.7 87.6 109.2 73.2 120.1 57.4 94.8 85.5 104.9 71.4 115.4 55.6 90.8 83.4 100.5 69.4 110.5 53.7
3025 85 103.6 101.9 113.4 87.0 125.0 71.7 100.2 100.1 109.3 85.1 120.5 69.9 96.5 96.5 105.1 83.1 115.9 68.1 93.1 93.1 100.7 81.0 111.1 66.3
90 107.8 107.8 113.8 98.9 125.4 84.1 104.7 104.7 109.8 97.0 120.9 82.4 101.5 101.5 105.6 95.0 116.3 80.6 98.1 98.1 101.3 93.0 111.3 78.2
75 104.1 80.8 115.1 64.6 126.7 46.8 100.3 78.8 110.8 62.8 121.9 45.2 96.2 76.7 106.3 60.9 116.9 43.5 92.0 74.5 101.7 58.9 111.7 41.7
80 104.6 93.8 115.5 78.2 126.9 60.9 100.8 91.8 111.3 76.3 122.2 59.1 96.9 89.7 106.5 74.0 117.4 57.3 92.8 87.6 102.0 71.9 112.4 55.4
3350 85 106.1 106.1 115.7 90.9 127.3 74.5 102.9 102.9 111.5 89.0 122.7 72.7 99.6 99.6 107.1 86.9 117.9 70.9 96.1 96.1 102.6 84.8 113.0 69.0
90 111.5 111.5 116.2 103.9 127.7 88.0 108.3 108.3 112.1 102.0 122.8 85.8 104.9 104.9 107.8 100.0 118.1 83.8 101.3 101.3 103.4 98.0 113.2 81.8
75 106.0 83.8 116.9 66.6 128.5 47.7 102.0 81.8 112.5 64.7 123.5 46.0 97.8 79.7 107.9 62.8 118.4 44.3 93.5 77.5 103.2 60.8 113.0 42.4
80 106.6 97.8 117.4 81.1 128.8 62.6 102.7 95.8 112.7 78.8 124.0 60.8 98.7 93.8 108.2 76.7 119.0 58.9 94.5 91.6 103.6 74.6 113.9 57.0
3675 85 109.1 109.1 117.6 94.7 129.3 77.2 105.8 105.8 113.3 92.7 124.5 75.4 102.4 102.4 108.8 90.6 119.6 73.5 98.7 98.7 104.2 88.5 114.5 71.6
90 114.7 114.7 118.3 108.7 129.4 91.1 111.3 111.3 114.1 106.8 124.7 89.2 107.8 107.8 109.8 104.8 119.9 87.2 104.0 104.0 105.4 102.7 114.8 85.2
75 107.6 86.7 118.5 68.4 130.0 48.6 103.5 84.6 114.0 66.5 124.9 46.7 99.3 82.5 109.3 64.5 119.6 44.8 94.8 80.2 104.5 62.6 114.2 42.9
80 108.4 101.7 118.7 83.4 130.4 64.1 104.5 99.7 114.3 81.4 125.5 62.3 100.4 97.6 109.7 79.3 120.4 60.5 96.2 95.5 104.9 77.1 115.2 58.6
4000 85 111.8 111.8 119.3 98.2 130.9 79.7 108.4 108.4 114.9 96.2 126.1 77.9 104.8 104.8 110.3 94.1 121.1 76.1 101.1 101.1 105.6 92.0 115.5 73.6
90 117.6 117.6 120.2 113.3 131.2 94.5 114.1 114.1 116.0 111.4 126.4 92.5 110.4 110.4 111.6 109.4 121.4 90.5 106.5 106.5 106.6 106.6 116.3 88.4
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-5 — Gross Cooling Capacities (kW) TTA100A Condensing Unit with TWE100A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 29.9 22.7 33.0 19.7 36.4 13.5 28.8 22.2 31.8 19.2 35.1 13.0 27.6 21.6 30.6 18.7 33.7 12.5 26.4 20.9 29.2 18.1 32.2 12.0
27 30.0 26.2 33.2 22.0 36.5 17.3 28.9 25.6 32.0 21.4 35.2 16.8 27.8 25.0 30.7 20.9 33.8 16.3 26.6 24.4 29.4 20.3 32.4 15.7
5141
29 30.3 29.8 33.2 25.5 36.6 21.0 29.3 29.3 32.0 24.9 35.3 20.5 28.2 28.2 30.8 24.3 33.9 19.9 27.3 27.3 29.5 23.7 32.5 19.4
32 31.6 31.6 33.3 29.0 36.7 24.6 30.7 30.7 32.1 28.4 35.4 24.1 29.7 29.7 30.9 27.8 34.1 23.6 28.7 28.7 29.7 27.2 32.6 22.9
24 30.5 23.7 33.7 18.9 37.1 13.7 29.4 23.1 32.4 18.4 35.7 13.2 28.2 22.5 31.1 17.8 34.2 12.7 26.9 21.8 29.8 17.3 32.7 12.2
27 30.6 27.5 33.8 22.9 37.2 17.8 29.5 26.9 32.6 22.3 35.8 17.3 28.4 26.3 31.2 21.7 34.4 16.8 27.2 25.7 29.9 21.1 32.9 16.2
5692
29 31.1 31.1 33.9 26.6 37.3 21.8 30.1 30.1 32.7 26.0 35.9 21.3 29.2 29.2 31.4 25.5 34.5 20.8 28.1 28.1 30.0 24.8 33.1 20.2
32 32.6 32.6 34.0 30.4 37.4 25.8 31.7 31.7 32.8 29.9 36.0 25.1 30.7 30.7 31.6 29.3 34.6 24.5 29.7 29.7 30.3 28.7 33.1 23.9
24 31.0 24.5 34.2 19.5 37.6 14.0 29.9 24.0 32.9 18.9 36.2 13.5 28.6 23.3 31.6 18.4 34.7 13.0 27.4 22.7 30.2 17.8 33.1 12.4
27 31.2 28.6 34.4 23.7 37.7 18.3 30.1 28.1 33.0 23.1 36.3 17.8 28.9 27.5 31.7 22.5 34.9 17.3 27.7 26.8 30.3 21.8 33.4 16.7
6242
29 31.9 31.9 34.4 27.7 37.9 22.6 31.0 31.0 33.2 27.1 36.5 22.1 30.0 30.0 31.9 26.5 35.0 21.5 28.9 28.9 30.5 25.9 33.5 21.0
32 33.6 33.6 34.6 31.8 37.9 26.7 32.6 32.6 33.4 31.3 36.5 26.1 31.6 31.6 32.1 30.7 35.1 25.5 30.5 30.5 30.9 30.1 33.6 24.9
24 31.5 25.4 34.7 20.0 38.1 14.2 30.3 24.8 33.4 19.5 36.6 13.7 29.1 24.2 32.0 18.9 35.0 13.1 27.8 23.5 30.6 18.3 33.4 12.5
27 31.7 29.8 34.8 24.4 38.2 18.8 30.6 29.2 33.5 23.8 36.8 18.3 29.4 28.6 32.1 23.2 35.3 17.7 28.2 28.0 30.7 22.6 33.7 17.1
6797
29 32.7 32.7 34.9 28.8 38.3 23.3 31.7 31.7 33.6 28.2 36.9 22.8 30.7 30.7 32.3 27.6 35.4 22.3 29.6 29.6 30.9 26.9 33.8 21.5
32 34.4 34.4 35.2 33.2 38.4 27.7 33.4 33.4 34.0 32.6 37.0 27.1 32.3 32.3 32.7 32.0 35.5 26.5 31.2 31.2 31.2 31.2 34.0 25.9
Dry coil conditions. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Performance
Data System