Trane SS-PRC003-EN Air Conditioner User Manual


 
SS-PRC003-EN 15
Performance
Data System
Table PD-2 — Gross Cooling Capacities (MBh) TTA075A Condensing Unit with TWE100A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFMBulb616773 61 6773616773616773
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 82.1 66.3 90.5 55.2 99.3 36.7 79.5 65.0 87.6 54.0 95.9 35.6 76.2 63.4 84.0 52.6 92.0 34.3 72.3 61.5 80.0 51.0 87.6 32.8
2550 80 82.6 77.8 90.7 63.7 99.4 48.7 80.0 76.5 87.8 62.5 96.1 47.5 76.9 75.0 84.1 60.8 92.2 46.1 73.3 73.2 80.1 59.1 87.9 44.5
85 85.2 85.2 90.8 75.0 99.6 60.5 83.0 83.0 87.9 73.7 96.3 59.2 80.2 80.2 84.4 72.2 92.5 57.8 77.1 77.1 80.4 70.5 88.1 56.3
90 89.5 89.5 91.3 86.6 99.7 72.2 87.1 87.1 88.5 85.3 96.3 70.7 84.3 84.3 85.1 83.8 92.5 69.2 81.1 81.1 81.2 81.2 88.2 67.6
75 83.7 69.7 92.2 54.1 100.8 37.5 81.0 68.4 89.1 52.8 97.4 36.2 77.6 66.7 85.4 51.3 93.3 34.8 73.7 64.9 81.3 49.7 88.8 33.2
2850 80 84.5 82.4 92.2 66.7 101.0 50.5 81.9 81.2 89.2 65.4 97.6 49.2 78.6 78.6 85.5 63.8 93.6 47.8 75.3 75.3 81.4 62.1 89.2 46.2
85 88.1 88.1 92.4 79.2 101.2 63.4 85.7 85.7 89.4 77.9 97.7 62.1 82.8 82.8 85.8 76.4 93.8 60.7 79.5 79.5 81.8 74.6 89.4 59.2
90 92.5 92.5 93.3 92.0 101.2 75.9 90.1 90.1 90.1 90.1 97.8 74.6 87.1 87.1 87.2 87.2 93.9 73.1 83.7 83.7 83.8 83.8 89.5 71.4
75 85.1 72.9 93.5 56.0 102.0 38.0 82.2 71.6 90.3 54.8 98.5 36.8 78.8 69.9 86.6 53.3 94.4 35.4 74.8 68.0 82.3 51.6 89.8 33.8
3150 80 86.0 86.0 93.6 69.7 102.3 52.1 83.6 83.6 90.4 68.3 98.7 50.9 80.6 80.6 86.7 66.7 94.7 49.5 77.3 77.3 82.5 64.9 90.2 47.9
85 90.5 90.5 93.8 83.3 102.5 66.2 88.0 88.0 90.8 82.0 98.9 64.9 85.0 85.0 87.1 80.4 94.8 63.2 81.6 81.6 83.0 78.6 90.4 61.5
90 95.1 95.1 95.2 95.2 102.5 79.6 92.5 92.5 92.6 92.6 99.0 78.3 89.4 89.4 89.5 89.5 95.1 76.8 85.9 85.9 86.0 86.0 90.6 75.1
75 86.2 76.0 94.6 57.9 103.1 38.6 83.3 74.6 91.3 56.6 99.4 37.3 79.9 73.0 87.5 55.1 95.3 35.9 75.9 71.1 83.0 53.1 90.6 34.3
3450 80 88.0 88.0 94.7 72.5 103.3 53.7 85.5 85.5 91.5 71.1 99.7 52.5 82.5 82.5 87.7 69.5 95.7 51.1 79.0 79.0 83.4 67.7 91.1 49.5
85 92.7 92.7 95.1 87.2 103.4 68.6 90.1 90.1 92.0 85.9 99.8 67.2 86.9 86.9 88.3 84.3 95.8 65.7 83.4 83.4 84.2 82.5 91.3 64.0
90 97.4 97.4 97.4 97.4 103.6 83.2 94.6 94.6 94.7 94.7 100.0 81.9 91.4 91.4 91.5 91.5 96.0 80.4 87.8 87.8 87.9 87.9 91.5 78.7
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-2 — Gross Cooling Capacities (kW) TTA075A Condensing Unit with TWE100A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
23.9 24.0 19.4 26.5 16.2 29.1 10.8 23.3 19.0 25.6 15.8 28.1 10.4 22.3 18.6 24.6 15.4 26.9 10.0 21.2 18.0 23.4 14.9 25.7 9.6
4332 26.7 24.2 22.8 26.6 18.7 29.1 14.3 23.4 22.4 25.7 18.3 28.1 13.9 22.5 22.0 24.6 17.8 27.0 13.5 21.5 21.4 23.5 17.3 25.7 13.0
29.4 25.0 25.0 26.6 22.0 29.1 17.7 24.3 24.3 25.7 21.6 28.2 17.3 23.5 23.5 24.7 21.1 27.1 16.9 22.6 22.6 23.5 20.6 25.8 16.5
32.2 26.2 26.2 26.7 25.3 29.2 21.1 25.5 25.5 25.9 25.0 28.2 20.7 24.7 24.7 24.9 24.5 27.1 20.3 23.7 23.7 23.8 23.8 25.8 19.8
23.9 24.5 20.4 27.0 15.8 29.5 11.0 23.7 20.0 26.1 15.5 28.5 10.6 22.7 19.5 25.0 15.0 27.3 10.2 21.6 19.0 23.8 14.5 26.0 9.7
4842 26.7 24.7 24.1 27.0 19.5 29.6 14.8 24.0 23.8 26.1 19.2 28.6 14.4 23.0 23.0 25.0 18.7 27.4 14.0 22.0 22.0 23.8 18.2 26.1 13.5
29.4 25.8 25.8 27.1 23.2 29.6 18.6 25.1 25.1 26.2 22.8 28.6 18.2 24.3 24.3 25.1 22.4 27.5 17.8 23.3 23.3 23.9 21.8 26.2 17.3
32.2 27.1 27.1 27.3 26.9 29.6 22.2 26.4 26.4 26.4 26.4 28.6 21.8 25.5 25.5 25.5 25.5 27.5 21.4 24.5 24.5 24.5 24.5 26.2 20.9
23.9 24.9 21.4 27.4 16.4 29.9 11.1 24.1 21.0 26.4 16.0 28.8 10.8 23.1 20.5 25.3 15.6 27.6 10.4 21.9 19.9 24.1 15.1 26.3 9.9
5352 26.7 25.2 25.2 27.4 20.4 29.9 15.3 24.5 24.5 26.5 20.0 28.9 14.9 23.6 23.6 25.4 19.5 27.7 14.5 22.6 22.6 24.2 19.0 26.4 14.0
29.4 26.5 26.5 27.5 24.4 30.0 19.4 25.8 25.8 26.6 24.0 29.0 19.0 24.9 24.9 25.5 23.5 27.8 18.5 23.9 23.9 24.3 23.0 26.5 18.0
32.2 27.8 27.8 27.9 27.9 30.0 23.3 27.1 27.1 27.1 27.1 29.0 22.9 26.2 26.2 26.2 26.2 27.8 22.5 25.1 25.1 25.2 25.2 26.5 22.0
23.9 25.2 22.3 27.7 17.0 30.2 11.3 24.4 21.9 26.7 16.6 29.1 10.9 23.4 21.4 25.6 16.1 27.9 10.5 22.2 20.8 24.3 15.6 26.5 10.0
5862 26.7 25.8 25.8 27.7 21.2 30.3 15.7 25.0 25.0 26.8 20.8 29.2 15.4 24.2 24.2 25.7 20.3 28.0 15.0 23.1 23.1 24.4 19.8 26.7 14.5
29.4 27.1 27.1 27.8 25.5 30.3 20.1 26.4 26.4 26.9 25.1 29.2 19.7 25.5 25.5 25.8 24.7 28.1 19.2 24.4 24.4 24.6 24.2 26.7 18.7
32.2 28.5 28.5 28.5 28.5 30.3 24.4 27.7 27.7 27.7 27.7 29.3 24.0 26.8 26.8 26.8 26.8 28.1 23.5 25.7 25.7 25.7 25.7 26.8 23.0
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity