Trane GAF2A0A30S21SA Air Conditioner User Manual


 
Pub. No. 22-1858-02 11
Electrical
Data
WIRING DATA
GAF2A0A18S11SA
Heater
Model
No.
No.
of
Circuits
240 VOLT 208 VOLT
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater - - - 2.0** 3 15 - - 2.0** 3 15
BAYECAA05++ 1 4.80 16400 20 28 30 3.60 12300 17.3 24 25
BAYECAA08++ 1 7.68 26200 32 43 45 5.76 19700 27.7 37 40
BAYECAA10++ 1 9.60 32800 40 53 60 7.20 24600 34.6 46 50
Note: ** Motor Amps
WIRING DATA
GAF2A0A24S21SA
Heater
Model
No.
No.
of
Circuits
240 VOLT 208 VOLT
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater - - - 1.3** 2 15 - - 1.3** 2 15
BAYECAA05++ 1 4.80 16400 20 27 30 3.60 12300 17.3 23 25
BAYECAA08++ 1 7.68 26200 32 42 45 5.76 19700 27.7 38 40
BAYECAA10++ 1 9.60 32800 40 52 60 7.20 24600 34.6 45 45
Note: ** Motor Amps
WIRING DATA
GAF2A0A30S21SA
Heater
Model
No.
No.
of
Circuits
240 VOLT 208 VOLT
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater - - - 1.7** 2 15 - - 1.7** 2 15
BAYECAA05++ 1 4.80 16400 20 27 30 3.60 12300 17.3 24 25
BAYECAA08++ 1 7.68 26200 32 42 45 5.76 19700 27.7 38 40
BAYECAA10++ 1 9.60 32800 40 52 60 7.20 24600 34.6 45 45
Note: ** Motor Amps