Trane GAF2A0A30S21SA Air Conditioner User Manual


 
10 Pub. No. 22-1858-02
AIRFLOW PERFORMANCE
GAF2A0A36S31SA
EXTERNAL STATIC
(in w.g)
Speed Taps - 230 VOLTS Speed Taps - 208 VOLTS
3 2 † 1 3 2 1
0 1191 1146 1094 1040 1015 964
0.1 1180 1132 1085 1033 1004 959
0.2 1158 1110 1065 1014 984 942
0.3 1119 1082 1035 979 958 916
0.4 1079 1045 1003 942 923 887
0.5 1040 1005 969 907 886 857
0.6 993 960 927 864 843 818
0.7 934 910 877 808 795 772
0.8 880 855 816 758 742 715
0.9 815 786 748 696 675 650
1.0 744 715 677 629 607 583
NOTES:
1. Values are with wet coil and without filters.
2. Contact your particular filter manufacturer for pressure drop data.
3. Electric heater pressure drop is negligible and is included within the airflow data.
4. † Factory Setting
GAF2A0A36S31SA MINIMUM HEATER AIRFLOW CFM
Heater Minimum Air Speed Tap
Without Heat Pump With Heat Pump
BAYECAA05LG1AA Tap 1 Tap 1
BAYECAA08LG1AA Available soon Available soon
BAYECAA10LG1AA Available soon Available soon
SEE AIR HANDLER NAMEPLATE OR PRODUCT DATA FOR EXCEPTIONS
Note: Heating and cooling speeds are the same, factory
set at Speed Tap #2.
Performance
Data
GAF2A0A36 AIRFLOW PERFORMANCE TABLE