Trane CAUC-C30 Fan User Manual


 
ACDS-PRC001-EN12
Electrical
Data
Unit Characteristics Condenser Fan Motor
Minimum Maximum
Allowable Circuit Fuse FLA LRA KW
Nominal Electrical Voltage Ampacity Size No./HP (Ea.) (Ea.) (Ea.)
Tons Model No. Characteristics Range (3),(5) (2),(5) (1) (1) (1) (1),(4)
CAUC-C20G 200-230/60/3 180-220/208-254 9.2 15 2/1.0 4.1 20.7 0.9
20 CAUC-C204 460/60/3 416-508 4.1 15 2/1.0 1.8 9.0 0.9
CAUC-C205 575/60/3 520-635 3.2 15 2/1.0 1.4 7.2 0.9
CAUC-C25G 200-230/60/3 180-220/208-254 13.3 20 3/1.0 4.1 20.7 0.9
25 CAUC-C254 460/60/3 416-508 5.9 15 3/1.0 1.8 9.0 0.9
CAUC-C255 575/60/3 520-635 4.6 15 3/1.0 1.4 7.2 0.9
CAUC-C30G 200-230/60/3 180-220/208-254 13.3 20 3/1.0 4.1 20.7 0.9
30 CAUC-C304 460/60/3 416-508 5.9 15 3/1.0 1.8 9.0 0.9
CAUC-C305 575/60/3 520-635 4.6 15 3/1.0 1.4 7.2 0.9
CAUC-C40G 200-230/60/3 180-220/208-254 17.4 20 4/1.0 4.1 20.7 0.9
40 CAUC-C404 460/60/3 416-508 7.7 15 4/1.0 1.8 9.0 0.9
CAUC-C405 575/60/3 520-635 6.0 15 4/1.0 1.4 7.2 0.9
CAUC-C50G 200-230/60/3 180-220/208-254 25.6 30 6/1.0 4.1 20.7 0.9
50 CAUC-C504 460/60/3 416-508 11.3 15 6/1.0 1.8 9.0 0.9
CAUC-C505 575/60/3 520-635 8.8 15 6/1.0 1.4 7.2 0.9
CAUC-C60G 200-230/60/3 180-220/208-254 25.6 30 6/1.0 4.1 20.7 0.9
60 CAUC-C604 460/60/3 416-508 11.3 15 6/1.0 1.8 9.0 0.9
CAUC-C605 575/60/3 520-635 8.8 15 6/1.0 1.4 7.2 0.9
CAUC-C80E 200/60/3 180-220 34 40 8/1.0 4.1 20.7 0.9
80 CAUC-C80F 230/60/3 208-254 34 40 8/1.0 4.1 20.7 0.9
CAUC-C804 460/60/3 416-508 15 20 8/1.0 1.8 9.0 0.9
CAUC-C805 575/60/3 520-635 12 15 8/1.0 1.4 7.2 0.9
CAUC-D10E 200/60/3 180-220 50 60 12/1.0 4.1 20.7 0.9
100 CAUC-D10F 230/60/3 208-254 50 60 12/1.0 4.1 20.7 0.9
CAUC-D104 460/60/3 416-508 22 25 12/1.0 1.8 9.0 0.9
CAUC-D105 575/60/3 520-635 17 20 12/1.0 1.4 7.2 0.9
CAUC-D12E 200/60/3 180-220 50 60 12/1.0 4.1 20.7 0.9
120 CAUC-D12F 230/60/3 208-254 50 60 12/1.01 4.1 20.7 0.9
CAUC-D124 460/60/3 416-508 22 25 12/1.0 1.8 9.0 0.9
CAUC-D125 575/60/3 520-635 17 20 12/1.0 1.4 7.2 0.9
Notes:
1. Electric information is for each individual motor.
2. Maximum fuse size is permitted by NEC 440-22 is 300 percent of one motor RLA plus the RLA of the remaining motors.
3. Minimum circuit ampacity equals 125 percent of the RLA of one motor plus the RLA of the remaining motors.
4. All Kw values taken at conditions of 45 F saturated suction temperature at the compressor and 95 F ambient.
5. Local codes may take precedence.
Table ED-1 — Electrical Data