Outdoor Unit
Installation Manual
3) Place unit on stand. Make sure it is level and
fasten securely to the stand.
• As shown in the figure below, install the
foundation and vibration-proof rubber pads to
directly support the bottom surface of the fixing
leg that is in contact with the bottom plate of the
outdoor unit.
• When installing the foundation for an outdoor
unit with downward piping, consider the piping
work.
• When water is to be drained through the drain hose,
attach the following drain nipple and waterproof
rubber cap, and use the drain hose (Inner diameter:
0.6” (16 mm)) sold on the market. Also seal the
screws securely with silicone material, etc., to
prevent water from leaking.
Some conditions may cause condensation or
dripping of water.
• When collectively draining discharged water
completely, use a drain pan.
For Reference
If a heating operation is to be continuously performed
for a long time under the condition that the outdoor
temperature is 32 °F (0 °C) or lower, draining defrosted
water may be difficult due to the bottom plate freezing,
resulting in trouble with the cabinet or fan.
GOOD
Mounting leg
Foundation
GOOD
NO GOOD
Foundation
Foundation
If only the end of the
mounting leg is
supported, it may
deform.
Do not support
the outdoor unit
only with the
mounting leg.
Bottom plate
of outdoor unit
Support the bottom surface of the
mounting leg that is in contact with
and underneath the bottom plate of
the outdoor unit.
Drain nipple
Waterproof rubber cap
(2pcs.)
Waterproof rubber
cap
Base plate
Drain nipple
11-EN