Toshiba RAV-SM1401AT-E Air Conditioner User Manual


 
10
RAV-SM561AT-E, RAV-SM801AT-E
Tightening of Connecting Part
(Unit: N•m)
Externally
threaded side
Internally
threaded side
Fix with spanner.
Tighten with torque wrench.
Half union or packed valve Flare nut
Flare at
indoor unit side
Flare at
outdoor unit side
Align the centers of the connecting pipes and
tighten the flare nut strong as far as possible with
your fingers.
Then fix the nut with a spanner and tighten it with
torque wrench as shown in the figure.
As shown in the figure, be sure to use a double
spanner to loosen or tighten the flare nut of the
valve at gas side. If using a single spanner, the nut
cannot be tightened with necessary tightening
torque.
On the contrary, use a single spanner to loosen or
tighten the flare nut of the valve at liquid side.
SM80 type valve at gas side
Pressure of R410A is higher than that of R22
(Approx. 1.6 times). Therefore, using a torque
wrench, tighten the flare pipe connecting sections
which connect the indoor/outdoor units at the
specified tightening torque. Incomplete connections
may cause not only a gas leak, but also a trouble of
the refrigeration cycle.
Do not apply refrigerating machine oil to
the flared surface.
4
REFRIGERANT PIPING
REQUIREMENT
1. Do not put the spanner on the cap. The valve
may be broken.
2. If applying excessive torque, the nut may be
broken according to some installation condi-
tions.
After the installation work, be sure to check gas leak
of connecting part of the pipes with nitrogen.
Outer diam. of copper pipe
6.4 mm (diam.)
9.5 mm (diam.)
12.7 mm (diam.)
15.9 mm (diam.)
Tightening torque
14 to 18 (1.4 to 1.8 kgf•m)
33 to 42 (3.3 to 4.2 kgf•m)
50 to 62 (5.0 to 6.2 kgf•m)
68 to 82 (6.8 to 8.2 kgf•m)
Flare nut
Spanner for work
Loosened
Tightened
Cap
Spanner
for fixing
Single spanner
is prohibited
NO GOOD