Toshiba RAV-SM1104BT-E Air Conditioner User Manual


 
– 86 –
(Example of 2-lines wiring)
(Real line: Wiring, Broken line: Refrigerant pipe)
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit wire.
Group address
Individual : 0000
Header unit : 0001
Follower unit : 0002
In case of group control
Outdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 23
Outdoor
1 2 3
Remote controller
Line address 1
Indoor unit address 1
Group address 1
1
2
2
1
3
2
2
1
2
2
2
2
Indoor
A B
1 2 3
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11 END
1
3, 6, 9
END 11
2, 5, 8
4, 7, 10
S
E
T
TIM
E
TIMER
S
E
T
TE
ST
FIL
TER
L
L
RE
S
E
T
TEMP
.
CL
FA
N
SA
VE
A
A
S
WIN
G/
FI
X
VEN
T
M
O
D
E
O
N
/
O
F
F
U
NI
T
LOUVER
T
9-3. Address Setup (Manual Setting from Remote Controller)
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
Set an indoor unit per a remote controller.
Turn on power supply.
1 Push
SET
+
CL
+
TEST
buttons
simultaneously for 4 seconds or more.
2 (Line address)
Using the temperature setup
/ buttons,
set 12 to the CODE No.
3 Using timer time / buttons, set the line address.
4 Push
SET
button. (OK when display goes on.)
5 (Indoor unit address)
Using the temperature setup
/ buttons, set 13 to the CODE No.
6 Using timer time / buttons, set 1 to the line address.
7 Push
SET
button. (OK when display goes on.)
8 (Group address)
Using the temperature setup
/ buttons, set 14 to the CODE No.
9 Using timer time / buttons, set 0000 to Individual, 0001 to Header unit, and 0002 to
Folloer unit.
10 Push
SET
button. (OK when display goes on.)
11 Push
TEST
button.
Setup completes. (The status returns to the usual stop status.)