Toshiba RAV-SM1104BT-E Air Conditioner User Manual


 
– 63 –
1
2
3
4
5
Red
White
Black
1
2
3
4
5
Red
White
Black
1
2
3
4
5
Red
White
Black
1
2
3
4
5
Red
White
Black
Winding Resistance of Fan Motor
Part name
Compact 4-way
Cassette type
Fan motor
STF-230-60-1R
Checking procedure
Measure the resistance value of each winding by using the tester.
Fan motor inside wiring diagram
Concealed Duct type
Fan motor
ICF-280-120-1C
(RAV-SM804BT
)
ICF-280-120-2C
(RAV-SM564BT
,
RAV-SM1104BT
,
RAV-SM1404BT
)
Ceiling type
Fan motor
SWF-280-60-1R
(RAV-SM564CT
)
SWF-280-60-2R
(RAV-SM804CT
)
Ceiling type
Fan motor
SWF-280-120-1R
(RAV-SM1104CT
,
RAV-SM1404CT
)
Position
Black – Red
Black – White
Red – White
Resistance value
87 ± 8.7
87 ± 8.7
87 ± 8.7
Under 20°C
Measure the resistance value of each winding by using the tester.
Fan motor inside wiring diagram
Measure the resistance value of each winding by using the tester.
Fan motor inside wiring diagram
Position
Black – Red
Black – White
Red – White
Resistance value
23.4 ± 2.4
23.4 ± 2.4
23.4 ± 2.4
Under 20°C
Position
Black – Red
Black – White
Red – White
Resistance value
53 ± 5.3
53 ± 5.3
53 ± 5.3
Under 20°C
Measure the resistance value of each winding by using the tester.
Fan motor inside wiring diagram
Position
Black – Red
Black – White
Red – White
Resistance value
37 ± 3.7
37 ± 3.7
37 ± 3.7
Under 20°C