Toshiba RAS-B10EKVP-E Air Conditioner User Manual


 
– 94 –
Diagnosis/Process flowchart Item
Preparation
Check
Check
Operation
Measure-
ment
Check
Stop
Check
Measure-
ment
Contents
Turn “OFF” the power supply
breaker, and remove 3P
connector which connects
inverter and compressor.
Check whether 25A fuse on
the control board assembly
is blown or not. (F01)
Turn on the power breaker,
and operate the air condi-
tioner in COOL mode by time
shortening.
Measure terminal voltage of
the electrolytic capacity.
760µF:400WV x 3
After operation, turn off the
power breaker after 2
minutes 20 seconds passed,
and discharge the electrolytic
capacitor by soldering iron.
Check voltage between motor
phases.
Is not winding between
#
-
$
,
$
-
%
, or
#
-
%
opened
or short-circuited?
Is not frame grounded with
#
,
$
, or
%
?
Summary
If fuse was blown, be sure
to check the electrolytic
capacitor and diode block.
(DB01)
Connect discharge
resistance (approx.
10040W) or soldering
iron (plug) between +, –
terminals of the electro-
lytic capacitor (760µF) of
C14 (with printed CAU-
TION HIGH VOLTAGE) on
P.C. board.
OK if 760µF
DC280 to 380V
Remove CN300 while
pushing the part indicated
by an arrow because
CN300 is a connector with
lock.
Resistance between
phases should be
approx. 55 to 77
Should be 10M or
more.
Replace
outdoor
fan motor.
Remove
connector of
compressor.
NG
NG
NG
NO
OK
OK
OK
YES
Check 25A fuse
(Part No.F01).
Does outdoor
fan rotate?
Replace fuse.
Check
electrolytic
capacitor, diode
block (DB01),
etc.
Check
electrolytic
capacitor, diode
(DB01),
etc.
Remove connector
CN300 of outdoor fan
motor, and using a
tester, check resistance
value between every
phases at motor side.
Check
terminal voltage
of electrolytic
capacitor.
BA
Discharging position
(Discharging period
10 seconds or more)
Plug of
soldering
iron
11-8. How to Diagnose Trouble in Outdoor Unit
11-8-1. Summarized Inner Diagnosis of Inverter Assembly
Table 11-8-1