Item
Operation flow and applicable data, etc.
Description
.
44
FILE NO. SVM-10020
19. FILTER When the elapsed time reaches 1000 hours after
Indicator
conditioner operation, the FILTER indicator lights.
After cleaning the filters, turn off the FILTER indicator.
How to Turn Off FILTER Indicator
Press [RESET] button on the indoor unit.
NOTE :
If [RESET] button is pushed while the FILTER indicator
is not lit, the indoor unit will start the automatic
operation.
.
18. Hi-POWER
([Hi-POWER] button on the remote controller
is pressed)
When [Hi-POWER] button is pressed while the indoor
unit is in Auto, Cooling or Heating operation, Hi-
Mode
POWER mark is indicated on the display of the remote
controller and the unit operates as follows.
1. Automatic operation
The indoor unit operates in according to the
current operation.
2. Cooling operation
remote controller does not change.)
The indoor unit's fan speed level increase 1 tap
The preset temperature drops 2.0°F (1ºC)
(The value of the preset temperature on the
3. Heating operation
remote controller does not change.)
The indoor unit's fan speed level increase 1 tap
The preset temperature increases 3.5°F (2ºC)
(The value of the preset temperature on the
4. The Hi-POWER mode can not be set in Dry
operation
The Hi-POWER operation will be cancelled
when press [Hi-POWER] button again.