Toshiba MMY-MAP0804HT8-E Air Conditioner User Manual


 
–30–
SMMS-i
Installation Manual
EN
SMMS-i
Installation Manual
<Corrective trial>
Start operation
1 Set the rotary switches on the interface P.C. board of the header outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1].
When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1].
2 Push and hold SW04 for more than 2 seconds.
NOTE
You cannot change the temperature setting during the test run.
Errors are detected as usual.
The unit does not perform test run for 3 minutes after turning the power on or stopping running.
Stop operation
1 Set the rotary switches on the interface P.C. board of the header unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
[A]
[C ]
[H ]
[B]
[ ]
[ ]
7-segment display
[A]
[C ]
[H ]
[B]
[ - C ]
[ - H ]
7-segment display
[A]
[U1]
[B]
[ ]
7-segment display
SW04
SW01 SW02
SW03
D600 D601 D602 D603 D604
SW05 SW15
Push switch
7-segment
display [A]
Push switch
7-segment
display [B]
Rotary switches
Interface PC board
59-EN 60-EN