Toshiba MMY-MAP0804HT8-E Air Conditioner User Manual


 
–18–
SMMS-i
Installation Manual
EN
SMMS-i
Installation Manual
Pipe holding bracket
Attach pipe holding brackets following the table below.
When using the piping cover When not using the piping cover
Diameter of pipe (mm) Interval
Ø15.9 - Ø19.1 2m
Ø22.2 - Ø41.3 3m
Piping/wiring panel
Drawing-out sideward
Close the opening with the
pipe cover.
Drawing-out
frontward
Drawing-out
downward
Piping/wiring panel
Drawing-out sideward
Fill silicon or putty into the
periphery of the pipes.
Drawing-out
frontward
Drawing-out
downward
8 ELECTRIC WIRING
WARNING
The appliance shall be installed in accordance with national wiring regulations.
Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
CAUTION
Perform wiring of power supply complying with the rules and regulations of the local electric company.
Do not connect 380V - 415V power to the terminal blocks for control cables (U1, U2, U3, U4, U5, U6); otherwise,
the unit may break down.
Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the
coating of cables may melt and cause an accident.
After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.
Follow the same structure for both the control wiring and refrigerate piping.
Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.
For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the
installation manual of each indoor unit.
Power supply specifications
Power wiring selection
Standard model
MCA: Minimum Circuit Amps
MOCP: Maximum Overcurrent Protection (Amps)
Do not bridge the power between outdoor units
through the equipped terminal blocks (L
1, L2, L3,
N).
Model
Power Supply
MCA
(A)
MOCP
(A)
Phase and frequency Nominal Voltage
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1404*
MMY-MAP1604*
3N~ 50Hz 380-400-415V
23.5
25.5
28.5
33.2
36.5
32
32
40
40
50
MMY-AP1814*
MMY-AP2014*
MMY-AP2214*
MMY-AP2414*
MMY-AP2614*
MMY-AP2814*
MMY-AP3014*
MMY-AP3214*
3N~ 50Hz 380-400-415V
49.0
51.0
54.0
57.0
62.0
65.0
69.7
73.0
63
63
63
63
80
80
80
100
Power supply for
outdoor units
NO GOOD
35-EN 36-EN