Toshiba HWS-802H-E Heat Pump User Manual


 
48
Toshiba
8-3.
Hydro Unit
Control
1)Capacity control (compressor, high-temperature release, low-temperature release)
This unit controls the compressor frequency and heater output so that the water outlet temperature matches the remote
controller set temperature.
1-1)Compressor control
Calculates the different between the remote controller set temperature (TSC_H, TSC_F) and the water outlet
temperature (Hot water supply: THO, Heating: TWO).
Sets the Hz signal correction amount that determines the number of compressor rotations by the temperature
difference.
Detects the number of compressor rotations.
Compares the Hz signal correction amount and the current operation Hz, and changes the compressor output
according to the difference.
* The control details are the same for hot water supply, heating, and cooling.
Item Operation flow and applicable data, etc.
Temperature settings
(TSC_H, TSC_F)
Hz signal correction
Number of compressor
rotation detection
Remote controller
Water outlet temperature
(THO, TWO)
Hydro unit
TSC_H-THO for hot water supply
TSC_F-TWO
for heating/cooling
Inverter output change
Hz signal correction Operation Hz
Number of compressor
rotation change
Compressor frequency changeable range 10 Hz to 70 Hz (802, 1402H-E)
10 Hz to 60 Hz (1102H-E)
+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 48 Monday, October 5, 2009 2:09 PM