Toshiba HWS-2101CSHM3-E(-UK) Heat Pump User Manual


 
101
Toshiba
9-4-3. Temperature sensor, temperature-resistance characteristic
table
TC, TWI, TWO, TFI, TTW, TE, TS, TO sensors TD, TL sensors
Typical value Typical value
Temperature
(°C)
Resistance value (k
Ω)
Temperature
(°C)
Resistance value (kΩ)
(Minimum) (Standard) (Maximum) (Minimum) (Standard) (Maximum)
-10 55.42
55.73
60.04 0 150.5 161.3 172.7
0 32.33 33.80 35.30 10 92.76 99.05 105.6
10 19.63 20.35 21.09 20 58.61 62.36 66.26
20 12.23 12.59 12.95 25 47.01 49.93 52.97
25 9.75 10.00 10.25 30 37.93 40.22 42.59
30 7.764 7.990 8.218 40 25.12 26.55 28.03
40 5.013 5.192 5.375 50 17.00 17.92 18.86
50 3.312 3.451 3.594 60 11.74 12.34 12.95
60 2.236 2.343 2.454 70 8.269 8.668 9.074
70 1.540 1.623 1.709 80 5.925 6.195 6.470
80 1.082 1.146 1.213 90 4.321 4.507 4.696
90 0.7740 0.8237 0.8761 100 3.205 3.336 3.468
100 0.5634 0.6023 0.6434
0-10
0
10
20
30
40
50
60
10 20 30 40 50 60 70 80 90 100
0
0 0
5
10
15
20
50
100
150
200
10 20 30 40 50 60 70 80 90 100
Resistance(kΩ)
Temperature(
°C)
TC, TWI, TWO, TFI, TTW, TE, TS, TO sensors
Resistance(kΩ)(50
°C
or lower)
Resistance(kΩ)(50
°C
or higher)
Temperature(
°C)
TD, TL sensors
* Since the TH sensor (outdoor unit heat-sink temperature sensor) is built in the
outdoor control board, the resistance value cannot be measured.
+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 101 Monday, October 5, 2009 2:09 PM