NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
4
3.Add the BTU/Hr of all the fuel burning appli-
ances in the space.
Vent-Free heater _______ BTU/Hr
Gas appliance #1* _______ BTU/Hr
Gas appliance #2 + _______ BTU/Hr
Total = _______ BTU/Hr
Example:
VFST Vent-free heater 32,000 BTU/Hr
Gas appliance #1 34,000 BTU/Hr
(water heater)
Total = 66,000 BTU/Hr
* Do not include direct-vent gas appliances.
Direct-vent is sealed combustion and draws
combustion air from the outdoors.
4. Compare the maximum BTU/Hr the space
can support with the actual amount of BTU/
Hr used.
_________ BTU/Hr
(max. the space can support)
_________ BTU/Hr
(actual amount of BTU/Hr used)
Example:
40,960 BTU/Hr
(max. the space can support)
66,000 BTU/Hr
(actual amount of BTU/Hr used)
The space in the above example is a confined
space because the actual BTU/Hr used is more
than the maximum BTU/Hr the space can sup-
port. You must provide additional fresh air.
b.Vent room directly to the outdoors. Refer to
National Fuel Gas Code, ANSI Z223.1 1992,
Section 5.3.
If the actual BTU/Hr used is less than the
maximum BTU/Hr the space can support, then
the space is an unconfined space. You will
need no additional fresh air ventilation for an
unconfined space.
LOCATION OF FIREPLACE
Carefully select the best location for installa-
tion of your VFST or VFPF series Unvented
Room Heater. The following factors should be
taken into consideration:
• Clearance to side wall, ceiling, woodwork
and windows.
• Location must not be affected by drafts
caused by kitchen exhaust fans, return air
registers for forced air furnaces/air condition-
ers, windows or doors.
• Installation must provide adequate ventila-
tion and combustion air.
• Do not install the VFST or VFPF series heat-
ers in a sleeping room or bathroom.
• Never obstruct the front opening of the
heater or restrict the flow of combustion and
ventilation air.
• This appliance may be installed in an after-
market* manufactured (Mobile) Home, where
not prohibited by state or local codes.
*Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer.
• Minimize modifications to existing con-
struction.
To ensure even heat distribution, it is best to
position the heater centrally within the rooms.
Make sure there is adequate ventilation where
the heater is installed. The gas appliance will
shut off if the oxygen level falls below 18%.
These appliances are uniquely suited for in-
stallations requiring a utility shelf positioned
directly above the fireplace. Utility shelves like
these are commonly used for locating televi-
sion sets and decorative plants.
To provide for the lowest possible shelf sur-
face, combustible materials used to support a
utility shelf directly above these appliances
should be positioned just above the appliance
top spacers. The minimum height from the
base of the appliance to the underside of com-
bustible materials used to construct a utility
shelf is 43 ¹⁄₄” (1099 mm).
The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
on or near conventional construction materials.
However, if installed on combustible materials,
such as carpeting, vinyl tile, etc., a metal or
wood barrier covering the entire bottom sur-
face must be used.
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed.
WARNING: MAINTAIN MINIMUM
CLEARANCES.
Do not install in the vicinity of gasoline or other
flammable liquids. The heater must be kept
clear and free from these combustible materi-
als and may not be located near where they are
stored.
Clearances
WARNING: DO NOT INSTALL VFST SE-
RIES UNVENTED ROOM HEATERS IN
SLEEPING QUARTERS, OR IN RECRE-
ATIONAL VEHICLES.
WARNING: DO NOT INSTALL THE VFST
UNVENTED ROOM HEATER:
• WHERE CURTAINS, FURNITURE,
CLOTHING OR OTHER FLAMMABLE
OBJECTS ARE LESS THAN 42" FROM
THE FRONT OF THE UNVENTED ROOM
HEATER.
• IN HIGH TRAFFIC AREAS.
• IN WINDY OR DRAFTY AREAS.
Ensure the minimum clearances shown in
Fig-
ures 1 and 2
are maintained.
Combustible mantles may be installed above
the appliance (as shown in
Figure 2
). The
mantle projection may be extended beyond 8" if
the height above the firebox opening is in-
creased proportionately as detailed by the in-
crements shown.
Your options are:
a.Rework equations adding the space of ad-
joining room(s). If the extra volume provides
an unconfined space, then remove door or
add ventilation grills between rooms. Refer
to National Fuel Gas Code, ANSI Z223.1
1992, Section 5.3.
WARNING: IF THE AREA IN WHICH THE
HEATER MAY BE OPERATED IS SMALLER
THAN THAT DEFINED AS AN UNCON-
FINED SPACE, PROVIDE ADEQUATE
COMBUSTION AND VENTILATION AIR BY
ONE OF THE METHODS DESCRIBED IN
THE NATIONAL FUEL GAS CODE, ANSI
Z223.1 1992, SECTION 5.3 OR APPLI-
CABLE LOCAL CODES.