Superior SSDVT-3530CNM Indoor Fireplace User Manual


 
4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Inlet Gas Supply Pressure
(all models)
Fuel # Minimum Maximum
Natural Gas
5.0" WC
(1.24 kPa)
10.5" WC
(2.61 kPa)
Propane
11.0" WC
(2.74 kPa)
13.0" WC
(3.23 kPa)
Table 4
Gas Pressure - All Models
Tables 4, 5 and 6 show the appliances' inlet
gas pressure requirements:
Manifold Gas Supply Pressure
(millivolt models)
Fuel # Low High
Natural
Gas
(Lo) 2.2" WC
(.55 kPa)
(Hi) 3.5" WC
(.87 kPa)
Propane
(Lo) 6.3" WC
(1.57 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Table 5
Manifold Gas Supply Pressure
(electronic models)
Fuel # Maximum Manifold Pressure
Natural
Gas
(Hi) 3.5" WC
(.87 kPa)
Propane
(Hi) 10.0" WC
(2.49 kPa)
Table 6
Test gauge connections are provided on the
front of the millivolt gas control valve, identi-
fi ed IN for the inlet and OUT for the manifold
side. A 1/8" NPT Test gauge connection
is provided at the inlet and outlet side of
the electronic gas control valve.
These appliances and their individual shut-off
valves must be disconnected from the gas
supply piping system during any pressure
testing of that system at pressures greater
than 1/2 psig (3.5 kPa).
These appliances must be isolated from the
gas supply piping system (by closing their
individual manual shut-off valve) during any
pressure testing of the gas supply piping
system at test pressures equal to or less than
1/2 psig (3.5 kPa).
Orifi ce Sizes - Sea Level to High Altitude
(All Models): These appliances are tested and
approved for installations at elevations of 0-4500
feet (0-1372 meters) above sea level using the
standard burner orifice sizes (marked with an
"*" in Table 7).
At the time of installation, it must be determined
if the appliance needs to be derated. Contact
your local gas supplier for deration requirements
for your area.
Deration - At higher elevations, the amount of
BTU fuel value delivered must be reduced by
either using gas that has been derated by the gas
company or by changing the burner orifi ce to a
smaller size as regulated by the local authorities
having jurisdiction and by the (USA) National
Fuel Gas Code NFPA 54 / ANSI Z223.1 - latest
edition or, in Canada, the CAN1-B149.1 and .2
codes - latest edition.
Burner Orifi ce Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
Natural
Gas
drill size
(inches)
Propane
Gas
drill size (inches)
SSDV-3530
2.3 mm (.090")
*
37L70 •
#54 (.055")
*
99K79 •
SSDV-4035
#36 (.1065")
*
18L40 •
#52
(.0635")
*
37G00 •
* Standard size installed at factory
• Part /Cat. Number
Table 7
Burn-in Period
During the fi rst few fi res of this appliance there
will be some odor due to the curing of the
paint and burning off of lubricants used in the
manufacturing process.
Depending on your use, the burn-in period may
take a few hours or a few days.
KEEP YOUR HOUSE WELL VENTILATED
DURING THE CURING PROCESS. THE ODOR
AND HAZE EMITTED DURING THE CURING
PROCESS CAN BE QUITE NOTICEABLE AND
MAY SET OFF A SMOKE DETECTOR.
If an optional blower is installed, Do not turn it
on during the Burn-In period.
A white fi lm may develop on the glass front
during the fi rst few fi res as part of the curing
process. The glass should be kept clean during
the fi rst two weeks of use to prevent the fi lm from
baking on (making it very diffi cult to remove).
See Cleaning Glass on Page 6.
Gas Controls / Control Compartment
Access
NOTE: The top louvered panel and the bottom
louvered control panel door remove and install
the same way as follows:
The gas controls can be found behind the control
compartment access door.
Removing Control Compartment Door:
Open the door by gently liftint it upward until the
hook catches on boths sides clear the locating
slots. Then pull door out to remove.
On millivolt systems, the piezo igniter, HI/LO
fl ame adjustment knob, and pilot and main
gas OFF/ON control knob are located below
the glass panel enclosure. The gas valve for
electronic systems is also located below the
glass enclosure panel. See Figure 1.
Reinstalling Control Compartment Door:
To reinstall, insert the hook catches on each
side of the door into the corresponding slots
in the control compartment opening, then
gently push forward and side down until it
locks in place.
Figure 1
OPENING CONTROL
COMPARTMENT DOOR
Control Valve
Lower Control
Compartment Door
Lift the Lower Control
Compartment Door
up and pull out to
remove.
Up
Out
Hook Catch
Operation of millivolt and electronic gas con-
trol systems are different. Before lighting and
operating your appliance determine if you have
a millivolt or electronic appliance. Familiarize
yourself with the gas control valve that your
appliance uses. Refer to Figure 1 for access
to the gas control valve.
Millivolt Appliances - Appliances with
Millivolt systems will be fi tted with the gas
control valve shown in Figures 4 or 5.
Electronic Appliances - Appliances with
electronic systems will be fi tted with the
electronic valve shown in Figure 3.
Millivolt Appliances - To light millivolt appli-
ances refer to the detailed lighting instructions
found on Pages 17 & 18 . Millivolt appliance
lighting instructions may also be found on the
pull out lighting instruction labels attached to
the gas control valve.
Millivolt appliances are fi tted with an OFF/ON
Rocker Switch located behind the control
compartment access door, below the appli-
ance front glass enclosure panel (see Figure 1
for location). Once the pilot is lit, the OFF/ON
rocker switch will control the appliance OFF/ON
burner operation. To operate: Toggle the switch
between its ON and OFF positions.