ELECTRICAL CONNECTIONS
THERMOSTAT WIRING AND LOCATION:
NOTICE: The thermostat must be mounted on a
vertical, vibration-free surface, free from air currents,
and in accordance with the furnished instructions.
Mount the thermostat approximately 5 feet (1.5m) above
the floor, in an area where it will be exposed to a free
circulation of average temperature air. Always refer to
the thermostat instructions, as well as our unit wiring
diagram, and wire accordingly. Avoid mounting the
thermostat in the following locations:
1. Cold Areas- Outside walls or areas where drafts
may affect the operation of the control.
2. Hot Areas- Areas where the sun's rays, radiation, or
warm air currents may affect the operation of the
control.
3. Dead Areas- Areas where the air cannot circulate
freely, such as behind doors or in corners.
THERMOSTAT HEAT ANTICIPATOR ADJUSTMENTS:
The initial heat anticipator setpoint should equal the
thermostat's current amperage draw when the unit is
firing. This setpoint should be measured for the best
results. Use the recommended ranges for a guide. If
further information is needed, consult your thermostat
manufacturer's instructions.
Recommended heat anticipator setting:
Unit Size: 30 thru 200 250 thru 400
For Tubular Units: 0.35 Amps 0.65 Amps
NOTICE: The start-up fan delay should not exceed
30 seconds from a cold start.
IMPORTANT: For all wiring connections, refer to the
wiring diagram shipped with your unit (either affixed
to the side jacket or enclosed in the installation
instructions envelope). Should any original wire
supplied with the heater have to be replaced, it must
be replaced with wiring material having a temperature
rating of at least 105° C.
Figure 8 - T834H-1009 or T834H-1017
Thermostat Wiring
Figure 7 - Low-voltage Thermostat Wiring
Single Stage
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC
POWER INCLUDING REMOTE
DISCONNECTS BEFORE
SERVICING. Failure to
disconnect power before
servicing can cause severe
personal injury or death.
Standard units are shipped for use on 115 volt, 60 hertz,
single phase electric power. The motor name-plate and
electrical rating of the transformer should be checked
before energizing the unit heater electrical system. All
external wiring must conform to the latest edition of
ANSI/NFPA No. 70, National Electrical Code, and
applicable local codes; in Canada, to the Canadian
Electrical Code, Part 1, CSA Standard C22.1.
Do not use any tools (i.e. screwdriver,
pliers, etc.) across terminals to check for power.
Use a voltmeter.
It is recommended that the electrical power supply to
each unit heater be provided by a separate, fused, and
permanently live electrical circuit. A disconnect switch of
suitable electrical rating should be located as close to
the gas valve and controls as possible. Each unit heater
must be electrically grounded in accordance with the
latest edition of the National Electrical Code, ANSI/NFPA
No. 70, or CSA Standard C22.1. Refer to Figures 7, 8
and 9.
RGW1W2
WR
G
Honeywell
T834H-1009
or
T834H-1017
Thermostat
Warning: Remove Jumper
between G and R
inside control panel
D6922