Hoisting clips are provided for ease of unloading and positioning the
fluid cooler. For overhead lifts or where additional safety is required,
safety slings should also be placed under the fluid cooler modules.
Under no circumstances should you combine the top and bottom
modules of modular models and attempt to hoist them at the same
time by utilizing the hoisting clips alone!
Fluid Cooler Installation
These installation instructions are intended to help you prepare be-
fore your fluid cooler arrives. If discrepancies exist between these
instructions and those shipped with the fluid cooler, the instructions
shipped with the fluid cooler will govern.
1. Prior to placement of the fluid cooler, confirm that the supporting
platform is level, and that the anchor bolt holes are correctly located
in accordance with Marley drawings.
2. Place bottom module on your prepared supports, aligning anchor bolt
holes with those in your supporting steel. Make sure that the orienta-
tion agrees with your intended piping arrangement. Attach fluid cooler
to supporting steel with 19mm diameter bolts and flat washers (by
others). See support drawing for location and quantity. Position flat
washers between the bolt head and the fluid cooler basin flange.
3. Before setting top module in place on bottom module, clean any
debris from the underside of the top module fill, skid and beams and
from the top of the bottom module and remove shipping cover from
bottom of top module—replace fasteners at side of module to prevent
leaks. Place top module on the top peripheral bearing surface (fac-
tory-installed gasket) of bottom module, aligning mating holes as it
is set in place. Attach top module to bottom module with fasteners
provided according to drawings shipped with your fluid cooler.
4. Connect the recirculation piping with rubber boot shipped with the
bottom module piping according to drawings shipped with you fluid
cooler.
5. Attach makeup water supply piping to appropriately-sized float valve
connection located in collection water basin side wall. Install the drain
and overflow according to drawings shipped with your fluid cooler.
If you wish to pipe overflow and drain water to a remote discharge
point, make those connections at this time also.
Note
Installation
Warning