SPX Cooling Technologies FSIG-TS-08A Humidifier User Manual


 
Specifications
Specification Value
Marley
/
Sigma F Series Cooling Tower
/
Specifications: Base
13
2.0 Thermal Performance:
2.1 The tower shall be capable of cooling
_____ GPM of water from ____ °F to
_____ °F at a design entering air wet-
bulb temperature of _____ °F. The cool-
ing tower manufacturer shall guarantee
that the tower supplied will meet
the specified performance conditions
when the tower is installed according
to plans.
2.2 The purchaser will arrange for an
on-site thermal performance test, to
be conducted in the presence of the
manufacturer and owner, and under
the supervision of a qualified, disinter-
ested third party in accordance with
CTI (Cooling Technologies Institute)
ATC-105 standards during the first
full year of operation. If the tower
fails to perform within the limits of
test tolerance, then the cooling tower
manufacturer will install additional cells
and/or make such corrections as are
agreeable to the owner and shall pay
for the cost of a retest. If the tower
still fails to perform as specified, then
the manufacturer shall make such
reimbursements as are appropriate and
agreeable to the owner to compensate
for the performance deficiency.
Your reason for purchasing a cooling tower is to obtain a con-
tinuing flow of cooled water as defined in the first paragraph at
left. If the tower that you purchase is incapable of performing
as specified, then you will not have received full value for your
money.
Bear in mind that the size—and cost—of a cooling tower var-
ies directly with its true thermal capability. This paragraph is
intended to protect you against either intentional or inadvertent
undersizing of the tower by the manufacturer. Judging the level
of performance of a cooling tower on critical processes is never
easy, and the potential risk of a non-performing cooling tower
usually causes the requirement for a mandatory acceptance test
to be very desirable.
Your contract with the successful bidder should establish the
acceptable remedies for missed performance, which might
include:
• The addition of one or more cells of tower, as necessary, to
bring the cooling tower to the specified level of performance.
This is usually limited to the scope of work as defined in the
specs, which means that you (the owner) will have to pay for
the additional basin, wiring, starters, piping, etc.
• The reimbursement of a portion of the total contract price equal
to the percentage deficiency in performance.
Under no circumstances should you allow the manufacturer to
repitch the fans to increase motor brake horsepower above that
shown in the proposal. That creates additional operating costs
that will continue for the life of the tower—and imposes no
penalty on the manufacturer.
Typical cooling tower performance curve.
55°
50° 55° 60° 65° 70° 75° 80°
5°F RANGE
10°F RANGE
15°F RANGE
60°
65°
70°
75°
COLD WATER TEMP. (°F)
WET BULB TEMP. (°F)
80°
85°
90°
95°