SPX Cooling Technologies 800 Fan User Manual


 
16
Maintenance
sibility to institute a program of water treatment and maintenance that will
minimize their impact. (See Water Treatment on pages 18 and 19.)
Tower Framework
Inspect for cracks and spalling and repair if necessary. Keep bolts tight in
the mechanical equipment supports. Maintain a positive Langelier index
in your circulating water. (See Water Treatment on pages 18 and 19.)
Drive Shaft
Check drive shaft alignment and condition of couplings every six months.
See the Drive Shaft Service Manual for correcting misalignment, balanc-
ing, or replacing parts.
Electric Motor
Lubricate and maintain each electric motor in accordance with the man-
ufacturer’s instructions. If repair work is necessary, contact the nearest
representative of the motor manufacturer. See Warranty Section of Marley
Service Manual on Electric Motors.
Fan
Inspect fan blade surfaces every six months. For detailed maintenance
information, refer to Marley Fan Service Manual.
Geareducer
Make weekly and monthly oil checks. Inspect internal parts during sea-
sonal oil change. Refer to the Geareducer Service Manual for detailed
maintenance instructions.
Cold Water Collection Basin
Inspect collection basin occasionally for cracks, leaks, and spalling and
repair if necessary. Maintain a positive Langelier index in your circulating
water. (See Water Treatment on pages 18 and 19.) Keep cold water out-
lets clean and free of debris. Make-up and circulating water controls must
operate freely and maintain the desired water quantity in the system.