Sears 153 Water Heater User Manual


 
Service and Adjustment
Tank (Sediment) Cleaning
Sediment build-up on the tank bottom may create varying
amounts of noise, and if left in the tank will cause premature
tank failure. In some water areas, you may not be able to drain
all sediment deposits by simply draining the tank. In these cases
Mag Erad (part no. 3515) can be used to help remove the sedi-
ment deposits. This may be ordered from the Sears Service
Center. For orderirlg, refer to the "Parrs Order List" section.
AWARNING ]
Soot build.upindicatesa problem that requires correction|
beforefurther use.Turn"OFF" gasto water heaterand leave|
"OFF" until repairs are made, becausefailure to correctthe/
causeof the sootingcanresult in a fire or explosioncausing|
DEATH,SERIOUSBODILYINJURY,OR PROPERTYDAMAGE.|
Venting System inspection
At least once a year a visual inspection should be made of the
venting system. You should look mr:
o
Obstructions which could cause improper venting. The com-
bustion and ventilation air flow must not be obstructed.
Damage or deterioration which could cause improper venting
or leakage of combustion products.
Rusted flakes around top of water heater.
AWARNING
Chemicalvapor corrosion of the flue andvent systemmay i
occurif air for combustioncontainscertain chemicalvapors.
Spraycan propellants,cleaningsolvents,refrigerator and air
conditionerrefrigerants,swlmmlngpool chemicals, calcium
and sodiumchloride,waxes,bleach,andprocesschemicalsare
typicalcompoundswhichare potentiallycorrosive.
Burner Cleaning
In the event your burner needs cleaning, use the following
instructions:
If inspection of the burner shows that deaning is required, turn
the gas control knob clockwise (_"_) to the "OFF" position,
depressing slightly.
NOTE: The knob cannot be turned from "PILOT" to "OFF"
unless knob is depressed slightly. DO NOT FORCE.
Loose deposits on or around the burner can be removed by care-
fully using the hose of a vacuum cleaner inserted through the
access door of the water heater. If the burner needs to be removed
for additional cleaning, calf the Sears Service Center to remove
and clean the burner and correct the problem that required the
burner to be cleaned.
AWARNING
Obstructedor deterioratedventsystemsmaypresenta serious
healthrisk orasphyxiation.
AWARNING
1Be sure the vent piping is properly connected to prevent
I escape of dangerousflue gasseswhich could causedeadly
[asphyxiation.
AWARNING
if after inspectionof the vent systemyou found sootingor
deterioration,somethingiswrong.Call the localgasutility to
correctthe problemandcleanor replace the flueandventing
beforeresuming operationof the water heater.
Burner Inspection
AWARNING {
Do notusethisapplianceif anypartof it hasbeenunderwater.
Immediately call a Sears ServiceTechnicianto inspectthe
appliance and to replace the gas control or any part of the
burner system which has been under water. {
At least once a year a visual inspection should be made of the
main burner and pilor burner. The drawing is for your reference.
You should check for sooting which is not normal and wil!
impair proper combustion.
2O
L.R Gas Control Valve & Burner
Assembly Replacement
Information
AWARNING
PROPANE (L.R) GAS CONTROL VALVE AND BURNER
ASSEMBLYREPLACEMENT INFORMATION.
For Propane (LP.) Gas Models Only:
Your water heater is equipped with a Propane (LR) gas
control valve and a main burner assemblywith left hand
threads for the following fittings and their connections.
(I) The connection between the manifold and the
gas control valve (A to B) are left hand threads.
(2) The connection between the main burner ori-
fice and the manifold (C to D) are left hand
threads. For ordering these replacement parts,
please refer to the "Parts Order List" section of
this manual.