Schneider Electric ACECFR40201SE Fan User Manual


 
EcoBreeze System Installation20
NOTE: Separate the drain line from the EcoBreeze Frame and the external drain line by a
50 mm (2 in.) air gap in order to prevent back up of contaminated water into the cooling system.
N
OTE: Pitch the external drain piping at a minimum of 25 mm (1 in.) per 3048 mm (10 ft)
towards the wastewater drain.
na3564a
AIR GAP